PHOENIX CONTACT FLT-SEC-P-T1-264/50-P FLT-SEC-P-T1-264/50-P 2907391 PHOENIX CONTACT Type 1 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FLT-SEC-P-T1-264/50-P 2907391 PHOENIX CONTACT Type 1 surge protection plug

FLT-SEC-P-T1-264/50-P

2907391

PHOENIX CONTACT

10 Pcs.

Type 1 surge protection plug Replacement connector for the lightning current arresters of the FLASHTRAB SEC PLUS 264 product series, for the L-N and L-PEN sections.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2907391
Packing unit5 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
Catalog pagePage 34 (C-4-2017)
GTIN4055626197210
Weight per Piece (excluding packing)259.900 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height46.6 mm
Width35.5 mm
Depth59.4 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

General

IEC test classificationI / II
T1 / T2
EN typeT1 / T2
IEC power supply systemTT
Mode of protectionL-N
L-PEN
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240 V AC (TN)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Nominal discharge current In(8/20) µs50 kA
Maximum discharge current Imax(8/20) µs100 kA
Impulse discharge current (10/350) µs, charge25 As
Impulse discharge current (10/350) µs, specific energy625 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp50 kA
Follow current interrupt rating Ifi50 kA
Short-circuit current rating ISCCR50 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.5 kV (at In)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 2.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
760 V AC (120 min / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring500 A (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type1CA
Maximum continuous operating voltage MCOV264 V AC
Nom. voltage240 V AC
Mode of protectionL-N
L-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Voltage protection rating VPR1500 V
Nominal discharge current In20 kA
Short-circuit current rating (SCCR)50 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


ETIM for 2907391 Earthing, lightning and surge protection (EC002496)
Feature Name Feature Value
Type of accessory/spare part (EF000215) Other
Accessory (EF013236) Yes
Spare part (EF013237) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.