PHOENIX CONTACT MINI MCR-2-FM-RC-PT MINI MCR-2-FM-RC-PT 2904508 PHOENIX CONTACT Monitoring module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-2-FM-RC-PT 2904508 PHOENIX CONTACT Monitoring module

MINI MCR-2-FM-RC-PT

2904508

PHOENIX CONTACT

1 Pcs.

Monitoring module Fault monitoring module with plug-in connection technology to evaluate and report collective fault monitoring system errors and to monitor supply voltages. Error signaling using an NC contact. Push-in connection technology, standard configuration

Automation > Accessories/spare parts for low-voltage switch technology
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2904508
Packing unit1 pc
Catalog pagePage 104 (C-5-2017)
GTIN4046356857390
Weight per Piece (excluding packing)96.300 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Description of the inputVoltage input for redundancy monitoring
Number of inputs1
Voltage input signal9.9 V DC ... 30 V DC

Output data

Number of outputs1
Voltage output signal9.6 V DC ... 29.7 V DC
Max. output current3.2 A

Switching output

Output nameSwitching output
Maximum switching voltage30 V DC
Max. switching current50 mA

Power supply

Supply voltage range12 V DC ... 24 V DC -20 % ... +25 % (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption< 16 mA (at 24 V DC)
Power consumption< 410 mW (at 24 V DC)

Connection data

Connection methodPush-in connection
Single conductor/terminal point, solid, with ferrule, min.0.14 mm²
Single conductor/terminal point, solid, with ferrule, max.2.5 mm²
Single conductor/terminal point, solid, without ferrule, min.0.14 mm²
Single conductor/terminal point, solid, without ferrule, max.2.5 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.2.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Stripping length10 mm

General

Maximum temperature coefficient< 0.01 %/K
Test voltage1500 V AC (50 Hz, 1 min.)
Status displayYellow LED (switching output)
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage50 V AC/DC (effective)
Test voltage input/output1.5 kV AC (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Housing materialPBT
Mounting positionany
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Certificate of classificationDNV GL 14445-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationBasic insulation according to EN 61010
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2904508 Low-voltage industrial controls and switchgear (EC002498)
Feature Name Feature Value
Type of accessory/spare part (EF000215) Other
Accessory (EF013236) Yes
Spare part (EF013237) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.