PHOENIX CONTACT ELR H5-IES-PT-24DC/500AC-3-P ELR H5-IES-PT- 24DC/500AC-3-P 2909556 PHOENIX CONTACT Hybrid motor starter as an alternative to a convention.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

ELR H5-IES-PT- 24DC/500AC-3-P 2909556 PHOENIX CONTACT Hybrid motor starter as an alternative to a convention..

ELR H5-IES-PT-24DC/500AC-3-P

2909556

PHOENIX CONTACT

1 Pcs.

Hybrid motor starter as an alternative to a conventional reversing contactor. Reverses 3~ AC motors up to 3 A, offers motor protection, ATEX, and emergency stop up to SIL 3. Possible group shut-down, supply, and relay extension via DIN rail connector. Hybrid motor starter as an alternative to the classic inverter protection circuit. It reverses motors from 3~ AC up to 3 A, offers motor protection, ATEX and emergency stop up to SIL 3. Possibility of group disconnection, power supply and extension of relays by means of rail bus connectors.

Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2909556
Packing unit1 pc
Catalog pagePage 26 (C-5-2019)
GTIN4055626406060
Weight per Piece (excluding packing)300.000 g
Custom tariff number85371098
Country of originDE (Germany)

Drawings



Block diagram

Block diagram

Back to top

Dimensions

Width22.5 mm
Height107.5 mm
Depth114 mm
Back to top

Ambient conditions

Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Degree of protectionIP20
Back to top

Device supply

Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS60 mA
Type of protectionSurge protection
Reverse polarity protection
Back to top

Input data

Input nameControl input: right/left and enable input
NoteThe enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),
unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function.
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC7 mA
Switching threshold9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Typical turn-off time< 30 ms
Type of protectionReverse polarity protection
Back to top

Output data load output

Output nameAC output
Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie3 A (AC-51)
3 A (AC-53a)
Mains frequency50/60 Hz
Load current range180 mA ... 3 A
Trigger characteristic in acc. with IEC 60947-4-2Class 10
Cooling time20 min. (for auto reset)
Leakage current0 mA
Type of protectionSurge protection
Back to top

Output data reply output

Output nameAcknowledge output
NoteConfirmation: floating change-over contact, signal contact
Contact type1 PDT
Switching capacity according to IEC 60947-5-12 A (24 V, DC13)
Back to top

Overspeed tripping

Operate threshold> 33 A
Response time< 0.5 s
Back to top

General

Switching frequency≤ 2 Hz (Load-dependent)
Mounting positionvertical (horizontal DIN rail, motor output below)
Mounting typeDIN rail mounting
Assembly instructionsalignable, for spacing see derating
Operating mode100% operating factor
Maximum power dissipation4.1 W
Minimum power dissipation0.88 W
Operating voltage displayGreen LED
Status displayYellow LED
IndicationRed LED
Back to top

Connection data

Connection nameControl circuits
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Back to top

Connection data 2

Connection nameLoad circuit
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Back to top

Insulation characteristics

Rated insulation voltage550 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
DesignationInsulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
InsulationSafe isolation (IEC 60947-1)
DesignationIsolation characteristics between the control input and control supply voltage to auxiliary circuit
InsulationSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Back to top

Standards and Regulations

DesignationStandards/regulations
Standards/regulationsEN 60947-1
EN 60947-4-2
EN 50495
EN ISO 13849
IEC 62061
IEC 61508
Back to top

Conformance/approvals

DesignationATEX
Identification I I (2) G [Ex db] [Ex eb] [Ex pxb]
 II (2) D [Ex tb] [Ex pb]
CertificatePTB 18 ATEX 3004
DesignationUL approval
CertificateNLDX.E228652
NRNT.E172140
DesignationSafety Integrity Level (SIL, IEC 61508)
Identification≤ 3
Additional textSafe shutdown
DesignationSafety Integrity Level (SIL, IEC 61508)
Identification2
Additional textMotor protection
DesignationPerformance Level (ISO 13849)
Identification≤ e
Additional textSafe shutdown
DesignationCategory (ISO 13849)
Identification≤ 3
Additional textSafe shutdown
Back to top

UL data

SCCR100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA3 A (480 V AC)
Group installation20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category codeNLDX / NRNT
Horsepower ratings0.5 hp (120 V AC / 208 V AC)
1.5 hp (277 V AC / 480 V AC)
Ambient temperature (operation)-25 °C ... 55 °C
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.027021100
eCl@ss 4.127021100
eCl@ss 5.027024000
eCl@ss 5.127024000
eCl@ss 6.027024000
eCl@ss 7.027024002
eCl@ss 8.027024002
eCl@ss 9.027370905
Back to top

ETIM

ETIM 2.0EC001037
ETIM 3.0EC001037
ETIM 4.0EC001037
ETIM 5.0EC001037
ETIM 6.0EC001037
ETIM 7.0EC001037
Back to top

ETIM for 2909556 Low-voltage industrial controls and switchgear (EC001037)
Feature Name Feature Value
Type of motor starter (EF009598) Reversing starter
With short-circuit release (EF006691) No
Rated control supply voltage DC (EF003980) 19.2 V
Voltage type for actuating (EF008242) DC
Rated operation current Ie (EF001443) 3 A
Rated operation current at AC-3, 400 V (EF009602) 3 A
Overload release current setting (EF002336) 0.18 A
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Temperature compensated overload protection (EF009604) No
Release class (EF006668) CLASS 10
Type of electrical connection of main circuit (EF006819) Spring clamp connection
Type of electrical connection for auxiliary- and control current circuit (EF006979) Spring clamp connection
Suitable for rail mounting (EF003972) Yes
Number of command positions (EF001372) 1
Suitable for emergency stop (EF001433) Yes
External reset possible (EF003426) Yes
Degree of protection (IP) (EF005474) IP20
Width (EF000008) 22.5 mm
Height (EF000040) 107.5 mm
Depth (EF000049) 114 mm