Multifunctional energy measuring device with integrated Modbus/TCP and EtherNet/IP™ interface for measuring electrical parameters in low-voltage installations up to 690 V.

Automation > Multifunction measuring instrument
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeEnergy measuring device
Product familyEMpro
Data management status
Article revision08

Electrical properties
Maximum power dissipation for nominal condition10 VA
Mains type3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor)
Electrical isolation
Test voltage4 kV AC (50 Hz, 60 s)
Pollution degree2
Electrical isolation Housing against all potentials IEC 61010-1
Standards/regulationsIEC 61010-1
Overvoltage categoryIII (300 V AC)
II (600 V AC)
InsulationReinforced insulation
Electrical isolation Supply against all other potentials IEC 61010-1
Standards/regulationsIEC 61010-1
Overvoltage categoryIII (300 V AC)
II (600 V AC)
InsulationReinforced insulation
Electrical isolation Voltage measurement input against all other potentials IEC 61010-1
Standards/regulationsIEC 61010-1
Measuring categoryIII (300 V AC)
II (600 V AC)
InsulationReinforced insulation
Electrical isolation Current measurement input against all other potentials
InsulationFunctional insulation
Electrical isolation Digital I/Os
InsulationFunctional insulation
Electrical isolation Communication interface
InsulationFunctional insulation
Supply
Supply voltage range100 V AC ... 400 V AC (±20 %)
150 V DC ... 250 V DC (±20 %)
Power consumption≤ 4 W
Nominal frequency50 Hz ... 60 Hz (AC sine)

Input data
General
Measuring principleTrue RMS value measurement (TRMS)
Measured valueAC sine (50 Hz/60 Hz)
Acquisition of harmonicsup to 63rd harmonic
Description of the inputDigital input in accordance with IEC/EN 61131-2 (type 3)
Number1
Voltage input signal24 V DC
0 V DC ... 30 V DC
Current input signal2 mA ... 15 mA
Protection250 mA (fast-blow)
Measurement: Voltage
Input nameVoltage measuring input V1, V2, V3
Input voltage range direct35 V AC ... 690 V AC (Phase/Phase)
20 V AC ... 400 V AC (Phase/neutral conductor)
Input voltage range via external transformers60 V AC ... 2000000 V AC (primary)
60 V AC ... 400 V AC (secondary)
Surge voltage capacity760 V AC (Phase/Phase)
Precision0.2 %
Power consumption< 2 VA
Measurement: Current
Input nameCurrent measurement I1, I2, I3
Input current1 A (secondary)
5 A (secondary)
Measuring range1 A ... 20000 A (primary)
Overload capacity6 A (Imax)
Response threshold from measuring range nominal value10 mA (1 A)
50 mA (5 A)
Precision0.2 %
Current overload50 A for 1 s
Power consumption< 0.5 VA
Measurement: Power
Precision0.5 %
Active energy (IEC 62053-22)Class 0.5 S
Reactive power (IEC 62053-23)Class 2
ANSI C12.20Class 0.5 S

Output data
Output descriptionDigital output in accordance with IEC/EN 61131-2 (type 3)
Number1
Current output signal≤ 100 mA
Voltage output signal24 V DC
Protection250 mA (fast-blow)

Connection data
Current / voltage / supply
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 6 mm²
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 10
Tightening torque0.5 Nm ... 0.6 Nm
Digital I/O / communication
Connection methodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section AWG26 ... 14
Tightening torque0.5 Nm ... 0.6 Nm

Interfaces
Data: Network interface
Communication protocolModbus/TCP
REST
Connection methodRJ45
Data: Network interface
Communication protocolEtherNet/IP™
Connection methodRJ45
Number of connections2
NoteDLR ready

Dimensions
Width96 mm
Height96 mm
Depth75 mm

Material specifications
Colorgray (RAL 7042)

Environmental and real-life conditions
Ambient conditions
Degree of protection (Housing)IP20 (Housing)
Degree of protection (Display)IP54 (Display (+ EEM-MA-IP))
Ambient temperature (operation)-10 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 70 °C
Altitude≤ 2000 m
Max. permissible relative humidity (operation)≤ 95 % (non-condensing)

Approvals
CE
CertificateCE-compliant
UKCA
CertificateUKCA-compliant
UL, USA/Canada
IdentificationUL/C-UL Listed UL 61010-1
UL data
Operating modeIndoor use
UL data
Operating modeIndoor use

Mounting
Mounting typePanel mount
Mounting positionFront panel installation, horizontal