| Direction of action | Line-Line & Line-Ground/Shield |
| Maximum continuous voltage UC(line-line) | ≤ 3.3 V DC (±60 V DC/PoE+) |
| Rated current | ≤ 1.5 A (25 °C) |
| Operating effective current ICat UC | ≤ 1 µA |
| Residual current IPE | ≤ 400 µA |
| Nominal discharge current In(8/20) µs (line-line) | 100 A |
| Nominal discharge current In(8/20) µs (line-ground) | 2 kA (per signal pair) |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Nominal pulse current Ian (10/700) µs (line-line) | ≤ 40 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | ≤ 160 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 85 V (PoE) |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 9 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
| Residual voltage at In(conductor-conductor) | ≤ 15 V |
| ≤ 100 V (PoE) |
| Voltage protection level Up(line-line) | ≤ 9 V (B2 - 1 kV / 25 A) |
| ≤ 100 V (B2 - 1 kV / 25 A - PoE) |
| Voltage protection level Up(line-earth) | ≤ 900 V (B2 - 4 kV / 100 A) |
| ≤ 700 V (C2 - 4 kV / 2 kA) |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | ≤ 1 dB (up to100 MHz/direct measuring) |
| ≤ 1 dB (up to 250 MHz/direct measuring) |
| ≤ 3 dB (up to 500 MHz/direct measuring) |
| Near-end crosstalk attenuation | ≥ 35 dB (250 MHz/100 Ω/link) |
| ≥ 45 dB (100 MHz / 100 Ω / Link) |
| ≥ 27 dB (500 MHz / 100 Ω / Link) |
| ≥ 39 dB (250 MHz/100 Ω/direct measuring) |
| Capacity (Core-Core) | typ. 12 pF (f= 1 MHz / VR= 0 V) |
| Capacity (Core-Earth) | typ. 2 pF (f= 1 MHz / VR= 0 V) |
| Surge protection fault message | none |
| Impulse durability (line-line) | B2 - 1 kV / 25 A |
| Impulse durability (line-earth) | B2 - 4 kV / 100 A |
| C2 - 4 kV / 2 kA |
| D1 - 1 kA |