| Product Type | Variable Speed Starter |
| Product Family | CONTACTRON |
| Operating elements | Key |
| Selector | |
| Insulation characteristics | |
| Degree of pollution | 2 |
| Number of phases | 3 |
| Network | |
| Number of phases | 3 |
| Input voltage | 380 V AC |
| 400 V AC | |
| 480 V AC | |
| Input voltage range | 220 V AC ... 480 V AC -15 % ... +10 % |
| Frequency | 47 Hz ... 63 Hz |
| Rated current | 1 A (without mains choke) |
| 0.9 A (with mains choke) | |
| Motor rated power | 0.25 kW |
| Apparent power | 0.6 kVA |
| Rated output current (IN) | 0.9 A (4 kHz) |
| 0.6 A (8 kHz) | |
| 0.4 A (16 kHz) | |
| Output Frequency | 0 Hz ... 500 Hz |
| Power dissipation | 14 W (2 kHz) |
| 18 W (4 kHz) | |
| 18 W (8 kHz) | |
| 17 W (16 kHz) | |
| 9 W (Standby) | |
| Output current | ≤ 1.35 A (180 s) |
| ≤ 0.675 A (180 s, during restore time) | |
| ≤ 1.62 A (15 s) | |
| ≤ 0.45 A (15 s, during recovery time) | |
| Reset Time | 150 s (180 s) |
| 12 s (15 s) | |
| Overload Time | 30 s (180 s) |
| 3 s (15 s) | |
| Discharge time | 3 min. (Intermediate Circuit Capacitors) |
| Switching | |
| Output Name | Relay output |
| Contact Switching Type | 1 diverter contact |
| Max. switchable voltage | 125 V AC |
| 30 V DC | |
| Max. inrush current | 3 A |
| Min. Insertion Current | 10 mA (5 V DC) |
| Conductor cross-section AWG | (converted according to IEC) |
| Power terminals | |
| Link | Push-in connection |
| Stripping length | 10 mm |
| Rigid conductor cross-section | 0.2 mm² ... 6 mm² |
| Flexible conductor cross-section | 0.2 mm² ... 6 mm² |
| 0.2 mm² ... 4 mm² (with lug) | |
| Conductor cross-section AWG | 24 ... 10 |
| Control Terminals | |
| Link | Push-in connection |
| Stripping length | 10 mm |
| Rigid conductor cross-section | 0.2 mm² ... 1.5 mm² (with lug) |
| Flexible conductor cross-section | 0.2 mm² ... 1.5 mm² |
| 0.2 mm² ... 0.75 mm² | |
| Conductor cross-section AWG | 24 ... 16 |
| Hole | |
| Diameter | 5.5 mm |
| width | 35 mm |
| height | 210 mm |
| Depth | 175 mm |
| length | ≤ 50 m (Motor cable length (EMC category C2 compliant)) |
| ≤ 50 m (Motor cable length (EMC category C3 compliant)) | |
| ≤ 50 m (Motor cable length (without EMC compliance)) | |
| Environmental conditions | |
| Degree of protection (IP) | Ip20 |
| Degree of protection (NEMA) | NEMA 1 |
| Ambient temperature (operating) | -20 °C ... 55 °C (without current derating) |
| -20 °C ... 60 °C (with linear current derating) | |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Elevated position | ≤ 2000 m |
| > 2000 m (with derating) | |
| Permissible humidity (operation) | 90 % (non-condensing) |
| Permissible humidity (storage/transport) | 95 % (non-condensing) |
| Shocks (exercise) | 15g, 11ms |
| Vibration (exercise) | 0.075 mm / 1g |
| Air pressure (operation) | 86 kPa ... 106 kPa |
| Air pressure (transport and storage) | 70 kPa ... 106 kPa |
| Safety Integrity Level (SIL, IEC 61800-5-2) | |
| Marking | 3 |
| Performance Level (EN ISO 13849) | |
| Marking | and |
| Category (ISO 13849) | |
| Marking | 4 |
| Standards/Provisions | IEC 61800-5-1 |
| IEC 61800-3 |
| Mounting type | Rail Mounting |
| Wall Mounting |
| Feature Name | Feature Value |
|---|---|
| Mounting method (EF000003) | Other |
| Colour (EF000007) | Grey |
| RAL-number (EF000116) | 7042 |
| Nominal current (EF000001) | 1 A |
| Number of phases (EF000351) | 3 |
| Power control stepless (EF000661) | Yes |
| Number of steps (EF002426) | 2 |
| Basic element without cover (EF008182) | No |
| Method of operation (EF000006) | Push button/touch control button |
| Lighting (EF000134) | None |
| Switching contact (EF001141) | Yes |
| With temperature sensor (EF006034) | No |
| Height (EF000040) | 210 mm |
| Width (EF000008) | 35 mm |
| Depth (EF000049) | 175 mm |
| Degree of protection (IP) (EF005474) | IP20 |