PHOENIX CONTACT MINI MCR-2-TC-UI MINI MCR-2-TC-UI 2902055 PHOENIX CONTACT Thermocouple measuring transducer View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-2-TC-UI 2902055 PHOENIX CONTACT Thermocouple measuring transducer

MINI MCR-2-TC-UI

2902055

PHOENIX CONTACT

1 Pcs.

Thermocouple measuring transducer Configurable temperature converter with plug-in connection technology for connecting thermocouples. Configurable via DIP switch or software. Screw connection technology, standard configuration

Automation > Temperature transformer
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2902055
Packing unit1 pc
Catalog pagePage 82 (C-5-2017)
GTIN4046356649766
Weight per Piece (excluding packing)126.800 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Configurable/programmableYes
Sensor types that can be used (TC)B, C, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L
Temperature measuring range-250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches)

Output data

Number of outputs1
Configurable/programmableYes
Voltage output signal0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10 V (via DIP switch)
10 V ... 0 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Current output signal0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
20 mA ... 0 mA (via DIP switch)
20 mA ... 4 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Max. output voltageapprox. 12.3 V
Max. output current24.6 mA
Short-circuit current< 31.5 mA
Load/output load voltage output≥ 10 kΩ
Load/output load current output≤ 600 Ω (at 20 mA)
Ripple< 10 mVrms
< 10 mVrms(at 600 Ω)

Power supply

Supply voltage range9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption32.7 mA (24 V DC)
66.8 mA (12 V DC)
Power consumption≤ 850 mW (at IOUT= 20 mA, 9.6 V DC, 600 Ω load)

Connection data

Connection methodScrew connection
Single conductor/terminal point, solid, with ferrule, min.0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Stripping length10 mm
Screw threadM3

General

Transmission error thermocouples0.1% * 600 K / set measuring range; 0.1% > 600 K (C, E, J, K, N, T, L, U, M Gost, L Gost)
0.2 % * 600 K / set measuring range; 0.2 % > 600 K (B, R, S, A1, A2, A3)
0.2% * 600 K / set measuring range; 0.2% > 600 K (E, J, K, N, T, L, U, M Gost, L Gost); Highspeed Mode
0.4% * 600 K / set measuring range; 0.4% > 600 K (B, R, S, A1, A2, A3); Highspeed Mode
Maximum temperature coefficient≤ 0.01 %/K
Typical cold point errors2 K (2 K + (0,2 K * ΔT))
Protective circuitTransient protection
Electrical isolationReinforced insulation in accordance with IEC 61010-1
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage300 V (effective)
Test voltage, input/output/supply3 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Certificate of classificationDNV GL 14445-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value0.06 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value0.1 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value0.05 %

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationReinforced insulation in accordance with IEC 61010-1
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2902055 Sensors (EC002919)
Feature Name Feature Value
Measuring range (EF001836) -250 °C
Analogue output 0 mA ... 20 mA (EF006808) No
Analogue output 4 mA ... 20 mA (EF006810) No
Analogue output 0 V ... 2 V (EF009886) No
Analogue output 0 V ... 5 V (EF009887) Yes
Analogue output 0 V ... 10 V (EF006807) Yes
Analogue output 2 V ... 10 V (EF009888) No
With switching output (EF005225) No
Modular version (EF001126) Yes
Integrated configuration function (EF003064) Yes
EMC-version (EF001062) Yes
Ambient temperature (EF002386) 70 °C
Weight (EF000167) 0.116 kg

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.