PHOENIX CONTACT MINI MCR-RTD-UI-NC MINI MCR-RTD-UI-NC 2902849 PHOENIX CONTACT Resistance thermometer measuring transducer View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-RTD-UI-NC 2902849 PHOENIX CONTACT Resistance thermometer measuring transducer

MINI MCR-RTD-UI-NC

2902849

PHOENIX CONTACT

1 Pcs.

Resistance thermometer measuring transducer Configurable temperature converter for the connection of 2, 3, 4 conductor resistance heaters and transmitters. Configurable via DIP switches or with the extended functionality by software. Screw connection, standard configuration.

Automation > Temperature transformer
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2902849
Packing unit1 pc
Catalog pagePage 103 (C-7-2015)
GTIN4046356689205
Weight per Piece (excluding packing)93.700 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Configurable/programmableYes
Sensor types (RTD) that can be usedPt, Ni, Cu sensors
Linear resistance measuring range0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range)
Sensor input currentapprox. 200 µA
Temperature measuring range-200 °C ... 850 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches)
Connection technology2, 3, 4-wire

Output data

Number of outputs1
Configurable/programmableYes
Voltage output signal0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. output voltageapprox. 12.3 V
Max. output current24.6 mA
Load/output load voltage output10 kΩ
Load/output load current output500 Ω (at 20 mA)
Ripple< 20 mVPP
< 20 mVPP(at 500 Ω)

Power supply

Supply voltage range9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption< 27 mA (at 24 V DC)
Power consumption≤ 700 mW (at IOUT= 20 mA, 9.6 V DC, load 500 Ω)

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length12 mm
Screw threadM3

General

Transmission error resistance thermometer0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)
Transmission error resistance-type sensor2 Ω
Maximum temperature coefficient0.01 %/K
Status displayLED red
Protective circuitTransient protection
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage50 V AC/DC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Certificate of classificationDNV GL 14085-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value0.04 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value0.1 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value0.02 %

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationBasic insulation according to EN 61010
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2902849 Sensors (EC002919)
Feature Name Feature Value
Measuring range (EF001836) -200 °C
Analogue output 0 mA ... 20 mA (EF006808) No
Analogue output 4 mA ... 20 mA (EF006810) No
Analogue output 0 V ... 2 V (EF009886) No
Analogue output 0 V ... 5 V (EF009887) Yes
Analogue output 0 V ... 10 V (EF006807) Yes
Analogue output 2 V ... 10 V (EF009888) No
With switching output (EF005225) No
Modular version (EF001126) Yes
Integrated configuration function (EF003064) Yes
EMC-version (EF001062) Yes
Ambient temperature (EF002386) 65 °C
Weight (EF000167) 0.0937 kg

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.