| AC Operation | |
| Input voltage range | 3x 400 V AC ... 480 V AC -15 % ... +10 % |
| Frequency | 50 Hz ... 60 Hz ±10 % |
| Input current | 3x 232 A |
| Configuring the Power Network | Star Mesh (TN-S, TT) |
| Rated power | 150 kW |
| Relay signal | |
| Identifying Connections | Temperature Sensor (OTD) |
| Function | Operational Status Forwarding |
| Changeover contact (potential-free) | Contact open at rest |
| Switchable voltage | 30 V DC |
| Current Rating | 1 A |
| Relay signal | |
| Identifying Connections | Surge Protection (SPD) |
| Function | Operational Status Forwarding |
| Changeover contact (potential-free) | Contact open at rest |
| Switchable voltage | 30 V DC |
| Current Rating | 1 A |
| External periphery power supply | |
| Number of outputs | 5 |
| Output voltage range | 3x 400 V AC ... 480 V AC (L1... L3) |
| External periphery power supply | |
| Number of outputs | 1 |
| Output voltage range | 3x 400 V AC ... 480 V AC (L1... L3, N) |
| Input power | |
| Denomination | Input power |
| Conductor connection | |
| Connection Type | T-LOX articulated lever connection |
| flexible with ferrule without plastic collar | 0.25 mm² ... 2.5 mm² |
| flexible ferrule with plastic collar | 0.25 mm² ... 1.5 mm² |
| Length of the section to be stripped | 25 mm |
| Output power | |
| Denomination | Output power |
| Conductor connection | |
| Connection Type | Push-in spring connection |
| rigid | 1.5 mm² ... 16 mm² |
| flexible | 1.5 mm² ... 16 mm² |
| Length of the section to be stripped | 18 mm |
| Signals | |
| Denomination | Signals |
| Conductor connection | |
| Connection Type | Push-in spring connection |
| rigid | 0.2 mm² ... 4 mm² |
| flexible with ferrule without plastic collar | 0.25 mm² ... 1.5 mm² |
| flexible ferrule with plastic collar | 0.25 mm² ... 2.5 mm² |
| rigid (AWG) | 24 ... 12 |
| Length of the section to be stripped | 10 mm |
| Galvanic isolation between input and output | no |
| Product Type | AC Splitter Module |
| Product Family | CHARX power distribute |
| Internal fans | Yes |
| Flow direction | front to back |
| Insulation characteristics | |
| Security class | The |
| Degree of pollution | 2 |
| Item Dimensions | |
| width | 483 mm |
| height | 134 mm |
| Depth | 598 mm |
| Rack unit | 3 HE |
| Mounting type | 19" rack mount |
| Housing Material | Zn-Al Alloy |
| Environmental conditions | |
| Degree of protection | Ip20 |
| Ambient temperature (operating) | -25 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| height | ≤ 2000 m |
| Permissible humidity (operation) | ≤ 95 % (non-condensing) |
| Noise level | < 60 dB (1 m) |
| Overvoltage Category | |
| IEC 60664-1 | Iii |
| Combinations of low-voltage switching devices - Part 7: Combinations of switching devices for certain applications | |
| Standard Definition | Combinations of low-voltage switching devices - Part 7: Combinations of switching devices for specific applications such as maritime applications, campsites, markets, electric vehicle charging stations |
| Standards/Regulations | IEC 61439-7 |
| UL Specifications | |
| Rated Stray Current IN | 20 kA |
| Electromagnetic interference requirements Noise emission | EN 61000-6-3 |
| Electromagnetic Interference Requirements Interference Immunity | EN 61000-6-1 |
| Feature Name | Feature Value |
|---|---|
| Type of accessory/spare part (EF000215) | Other |
| Accessory (EF013236) | No |
| Spare part (EF013237) | No |