View larger
BLT-T2-1S-305-UT
1078433
PHOENIX CONTACT
10 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 1078433 |
|---|---|
| Packing unit | 1 |
| Catalog page | Page 76 (C-4-2019) |
| GTIN | 4055626793344 |
| Custom tariff number | 85354000 |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
| IEC test classification | II / III |
|---|---|
| EN type | T2 / T3 |
| IEC power supply system | TN-S |
| TT | |
| SPD failure behavior | OCM |
| Accessibility | Accessible |
| Installation location of the disconnect device | Internal |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | 4 mm screw |
| Color | light grey RAL 7035 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Distance between live and grounded parts | 3 mm |
| Flammability rating according to UL 94 | V-0 |
| Protection class | I |
| Nominal voltage UN | 100 V AC ... 230 V AC (TN-S) |
|---|---|
| 100 V AC ... 230 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 305 V AC |
| Maximum continuous operating voltage UC(L-PE) | 265 V AC |
| Maximum continuous voltage UC(N-PE) | 265 V AC |
| Rated load current IL | 16 A |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (L-N) | 5 kA |
| Nominal discharge current In(8/20) µs (L-PE) | 5 kA |
| Nominal discharge current In(8/20) µs (N-PE) | 10 kA |
| Maximum discharge current Imax(8/20) µs (L-N) | 10 kA |
| Maximum discharge current Imax(8/20) µs (L-PE) | 10 kA |
| Maximum discharge current Imax(8/20) µs (N-PE) | 20 kA |
| Combination wave UOC(L-N) | 10 kV |
| Combination wave UOC(L-PE) | 10 kV |
| Combination wave UOC(N-PE) | 20 kV |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A () |
| Short-circuit current rating ISCCR | 10 kA (6 A gG backup fuse) |
| 3 kA (16 A MCB B/C backup fuse) | |
| Voltage protection level Up(L-N) | ≤ 1.3 kV |
| Voltage protection level Up(L-PE) | ≤ 1.5 kV |
| Voltage protection level Up(N-PE) | ≤ 1.5 kV |
| TOV behavior at UT(L-N) | 336 V AC (5 s / withstand mode) |
| 440 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(L-PE) | 440 V AC (5 s / withstand mode) |
| 440 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 16 A (MCB B/C) |
| Max. backup fuse with branch wiring | 16 A (MCB B/C) |
| Connection method | Screw terminal blocks |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.6 Nm |
| Stripping length | 8 mm |
| 2 conductors with same cross section, stranded min. | 0.2 mm² |
| 2 conductors with same cross section, stranded max. | 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| 2 conductors with same cross section, solid min. | 0.2 mm² |
| 2 conductors with same cross section, solid max. | 1.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Feature Name | Feature Value |
|---|---|
| System configuration DC (EF009926) | No |
| System configuration IT (EF009927) | No |
| System configuration TN (EF009928) | No |
| System configuration TN-C (EF009929) | No |
| System configuration TN-C-S (EF009933) | No |
| System configuration TN-S (EF009930) | Yes |
| System configuration TT (EF009931) | No |
| System configuration other (EF009932) | No |
| Nominal discharge surge current (8/20) (EF004214) | 5 kA |
| Max. discharge surge current (8/20) (EF012274) | 10 kA |
| Max. continuous voltage AC (EF004198) | 305 V |
| Voltage protection level (EF003525) | 1.5 kV |
| Voltage protection level L-N (EF004236) | 1.3 kV |
| Voltage protection level N-PE (EF008796) | 1.5 kV |
| Max. overcurrent protection device, parallel connection (fuse) (EF015962) | 16 A |
| Max. overcurrent protection device, series connection (fuse) (EF015963) | 16 A |
| Short-circuit breaking capacity (Isccr) (EF012627) | 10 kA |
| Leakage-current free (EF016002) | No |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 0.2 mm² |
| Max. conductor cross section flexible (fine-strand) (EF008828) | 2.5 mm² |
| Signalling at the device (EF004241) | Optic |
| Category type 2 (EF004230) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |