PHOENIX CONTACT AXL F PWM2 1H AXL F PWM2 1H 1007352 PHOENIX CONTACT Axioline F, function module, pulse width modulation, transmission spee.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL F PWM2 1H 1007352 PHOENIX CONTACT Axioline F, function module, pulse width modulation, transmission spee..

AXL F PWM2 1H

1007352

PHOENIX CONTACT

1 Pcs.

Axioline F, function module, pulse width modulation, transmission speed in local bus 100 Mbps, IP20 degree of protection, including bus base module and Axioline F male connectors AxiolineF, Function module, Pulse width modulation, local bus transmission rate:100 MBit/s, protection rating:IP20, including bus socket module and AxiolineF connectors

Automation > Fieldbus, decentr. periphery - function-/technology module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Dimensions
Dimensional drawingehsjridawo.jpg
Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Notes
Note on application
Note on applicationOnly for industrial use

Interfaces
Axioline F local bus
Number of interfaces2
Connection methodBus base module
Transmission speed100 Mbps

System properties
Module
Input address area0 Byte
Output address area8 Byte
Required parameter data1 Byte
Required configuration data6 Byte

Output data
Signal
Output namePWM outputs
Operating modePWM, pulse generator, push-pull output
Connection methodPush-in connection
Connection technology2-conductor
Number of outputs2
Frequency range0 Hz ... 65535 Hz
Pulse duty factor0 % ... 100 %
Nominal output voltage24 V (UO- 1.1 V)
5 V DC
Nominal current INmax. 500 mA (at 24 V DC)
max. 10 mA (at 5 V DC)
Nominal load, ohmicmax. 12 W (at 24 V DC nominal voltage)
max. 50 mW (at 5 V DC nominal voltage)
Nominal load, inductivemax. 12 VA (at 24 V DC nominal voltage)
max. 50 mVA (at 5 V DC nominal voltage)
Nominal load, lampmax. 6 W (at nominal voltage)
Short-circuit-proofyes
Short-circuit currenttyp. 2.2 A (for approx. 1.2 µs, auto-retry after approx. 40 µs, 24 V output)
typ. 24 mA (5 V output)
Transient surge protectionyes

Product properties
Product typeI/O component
Product familyAxioline F
Typeblock modular
Mounting positionany (no temperature derating)
Scope of deliveryincluding bus base module and Axioline F connectors
Special propertiesPulse width modulation
Data management status
Article revision03
Insulation characteristics
Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Electrical properties
Maximum power dissipation for nominal condition2.05 W
Potentials: Axioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current drawmax. 150 mA
Potentials: Supply voltage input UO
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC including all tolerances, including ripple
Current drawmax. 1.1 A
Protective circuitSurge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 1 A fuse (for start-up only)
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.

Connection data
Connection technology
Connection nameAxioline F connector
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection methodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm
Axioline F connector
Connection methodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid0.2 mm² ... 1.5 mm²
Conductor cross section, flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-25 °C ... 60 °C
Degree of protectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Standards and regulations
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting
Mounting typeDIN rail mounting
Mounting positionany (no temperature derating)

ETIM for 1007352 PLC's (EC001601)
Feature Name Feature Value
Supply voltage AC 50 Hz (EF007532) 19.2 V
Supply voltage AC 60 Hz (EF007533) 19.2 V
Supply voltage DC (EF007534) 19.2 V
Number of functions (EF003244) 0
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) No
Supporting protocol for EtherCAT (EF017564) No
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) Yes
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) No
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) No
IO link master (EF007298) No
System accessory (EF004118) Yes
Function block restart blockage (EF007212) No
Function block automatic reset (EF007208) No
Contactor control function block (EF007467) No
Function block emergency stop (EF007211) No
Function block contactless working protection installation (EF007209) No
Function block affirm push button (EF007214) No
Function block 2-hand switching (EF007215) No
Function block operating mode selection (EF007210) No
Function block access control (EF007213) No
Degree of protection (IP) (EF005474) IP20
Fieldbus connection over separate bus coupler possible (EF004002) Yes
Frequency measurement (EF000599) No
Suitable for rail mounting (EF003972) Yes
Wall mounting/direct mounting (EF007020) No
Front built-in possible (EF007016) No
Rack-assembly possible (EF007018) No
Suitable for safety functions (EF001597) No
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Appendant operation agent (Ex ia) (EF004141) No
Appendant operation agent (Ex ib) (EF004142) No
Explosion safety category for gas (EF003997) None
Explosion safety category for dust (EF003998) None

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.