View larger
AXL F IMPULSE2 XC 1H
2702655
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2702655 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 123 (C-6-2017) |
| GTIN | 4055626269511 |
| Weight per Piece (excluding packing) | 134.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
| Dimensional drawing | |
|---|---|
| Width | 35 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
| Ambient temperature (operation) | -25 °C ... 60 °C (Standard) |
|---|---|
| -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 (per manufacturer's declaration) |
| Mounting type | DIN rail |
|---|---|
| Net weight | 134 g |
| Note on weight specifications | with connectors and bus base module |
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | max. 150 mA |
| Power consumption | max. 0.75 W |
| Designation | Supply voltage input UI |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC including all tolerances, including ripple |
| Current consumption | max. 30 mA (Supply of pulse interface, without encoder supply) |
| Power consumption | max. 0.72 W (Supply of pulse interface, without encoder supply) |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage | |
| Transient protection |
| Number of 24 V encoder supplies | 2 |
|---|---|
| Nominal output voltage | 24 V DC (UI- 0.5 V) |
| Voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current carrying capacity | typ. 500 mA |
| Type of protection | Surge protection |
| Short-circuit protection | |
| Transient protection |
| Input name | Digital inputs |
|---|---|
| Description of the input | EN 61131-2 types 1 and 3 |
| Connection method | Push-in connection |
| Connection technology | 1-wire |
| Number of inputs | 4 |
| Type of protection | Polarity reversal protection of the inputs |
| Input filter time | 250 µs |
| Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 11 V DC ... 30 V DC |
| Nominal input current at UIN | 2.4 mA |
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |
| Feature Name | Feature Value |
|---|---|
| Supply voltage DC (EF007534) | 19.2 V |
| Number of functions (EF003244) | 1 |
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 |
| Number of interfaces PROFINET (EF006932) | 0 |
| Number of HW-interfaces RS-232 (EF003021) | 0 |
| Number of HW-interfaces RS-422 (EF003022) | 0 |
| Number of HW-interfaces RS-485 (EF003023) | 0 |
| Number of HW-interfaces serial TTY (EF003024) | 0 |
| Number of HW-interfaces parallel (EF003026) | 0 |
| Number of HW-interfaces wireless (EF006933) | 0 |
| Number of HW-interfaces USB (EF003025) | 0 |
| Number of HW-interfaces other (EF003027) | 0 |
| With optical interface (EF003028) | No |
| Supporting protocol for EtherCAT (EF017564) | No |
| Supporting protocol for TCP/IP (EF003050) | No |
| Supporting protocol for PROFIBUS (EF003052) | Yes |
| Supporting protocol for CAN (EF003053) | No |
| Supporting protocol for INTERBUS (EF003054) | No |
| Supporting protocol for ASI (EF003051) | No |
| Supporting protocol for KNX (EF003055) | No |
| Supporting protocol for Modbus (EF003057) | No |
| Supporting protocol for Data-Highway (EF003058) | No |
| Supporting protocol for DeviceNet (EF003059) | No |
| Supporting protocol for SUCONET (EF003060) | No |
| Supporting protocol for LON (EF003017) | No |
| Supporting protocol for PROFINET IO (EF007525) | No |
| Supporting protocol for PROFINET CBA (EF007524) | No |
| Supporting protocol for SERCOS (EF006657) | No |
| Supporting protocol for Foundation Fieldbus (EF007522) | No |
| Supporting protocol for EtherNet/IP (EF007521) | No |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | No |
| Supporting protocol for DeviceNet Safety (EF007520) | No |
| Supporting protocol for INTERBUS-Safety (EF006662) | No |
| Supporting protocol for PROFIsafe (EF007526) | No |
| Supporting protocol for SafetyBUS p (EF007527) | No |
| Supporting protocol for other bus systems (EF003062) | No |
| IO link master (EF007298) | No |
| System accessory (EF004118) | Yes |
| Function block restart blockage (EF007212) | No |
| Function block automatic reset (EF007208) | No |
| Contactor control function block (EF007467) | No |
| Function block emergency stop (EF007211) | No |
| Function block contactless working protection installation (EF007209) | No |
| Function block affirm push button (EF007214) | No |
| Function block 2-hand switching (EF007215) | No |
| Function block operating mode selection (EF007210) | No |
| Function block access control (EF007213) | No |
| Degree of protection (IP) (EF005474) | IP20 |
| Fieldbus connection over separate bus coupler possible (EF004002) | Yes |
| Frequency measurement (EF000599) | No |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting/direct mounting (EF007020) | No |
| Front built-in possible (EF007016) | No |
| Rack-assembly possible (EF007018) | No |
| Suitable for safety functions (EF001597) | No |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Appendant operation agent (Ex ia) (EF004141) | No |
| Appendant operation agent (Ex ib) (EF004142) | No |
| Explosion safety category for gas (EF003997) | None |
| Explosion safety category for dust (EF003998) | None |