PHOENIX CONTACT AXL E EIP IOL8 DI4 M12 6P AXL E EIP IOL8 DI4 M12 6P 2701496 PHOENIX CONTACT Distributed I/O device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL E EIP IOL8 DI4 M12 6P 2701496 PHOENIX CONTACT Distributed I/O device

AXL E EIP IOL8 DI4 M12 6P

2701496

PHOENIX CONTACT

1 Pcs.

Distributed I/O device AxiolineE, EtherNet/IP™, M12 Quick Connect Technology, IO-Link Class A ports: 4, connection type: M12 Quick Connect Technology, connection technology: 3 conductors, IO-Link Class B ports: 4, connection type: M12 Quick Connect Technology, connection technology: 3 conductors, Digital inputs on pin 2 with Class A ports: 4, 24 VDC, connection technology: 3 conductors, Plastic housing, protection rating: IP65/IP67

Automation > Fieldbus, decentr. periphery - digital I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2701496
Packing unit1 pc
Catalog pagePage 195 (C-6-2017)
GTIN4046356763509
Weight per Piece (excluding packing)552.800 g
Custom tariff number85176200
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Dimensional drawing
Width60 mm
Height185 mm
Depth30.5 mm
Note on dimensionsThe height is 212 mm including fixing clips.
Drill hole spacing198.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Permissible humidity (storage/transport)5 % ... 95 %
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP65/IP67

General

Housing materialPocan®
Mounting typeWall mounting
Net weight552.8 g

Interfaces

DesignationEtherNet/IP™
No. of channels2
Connection methodM12 fast connection technology
Note on the connection methodD-coded
Designation connection pointCopper cable
Transmission speed10/100 Mbps (with auto negotiation)
Number of positions4

System limits of the bus coupler

DesignationEtherNet/IP™
Equipment typeEtherNet/IP™ slave
System-specific protocolsEtherNet/IP™ protocols ACD
EtherNet/IP™ protocols DLR
EtherNet/IP™ protocols IGMP v2
Protocols supportedSNMP v1
HTTP
TFTP
FTP
BootP
DHCP
SpecificationCIP Edition 3.11
EIP adaptation of CIP 1.12

Supply

DesignationModule electronics and sensors (US)
Connection methodM12 connector (T-coded)
Number of positions4
Supply voltage24 V DC
Nominal supply voltage range19.5 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 180 mA ±15 % (at 24 V DC)
DesignationActuators (UA)
Connection methodM12 connector (T-coded)
Number of positions4
Supply voltage24 V DC
Nominal supply voltage range18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 28 mA ±15 % (at 24 V DC)

Digital inputs

Input nameDigital inputs at pin 2 for type A ports
Description of the inputIEC 61131-2 type 1
Connection methodM12 connector, X01 ... X04 have double occupancy
Connection technology3-wire
Number of inputs4
Type of protectionOverload protection, short-circuit protection of sensor supply
Input filter time< 1000 µs
Input voltage range "0" signal-0.3 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Input frequency0.5 kHz
Nominal input current at UINtyp. 3 mA
Description of the inputIO-Link ports in digital input (DI) mode
Connection methodM12 connector, X01 ... X04 have double occupancy
Connection technology3-wire
Number of inputsmax. 8 (EN 61131-2 type 1)
Nominal input voltage UIN24 V DC
Input voltage range "0" signal-0.3 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input currenttyp. 3 mA
Sensor current per channelmax. 200 mA (from L+/L-)
Total sensor currentmax. 1.6 A (from L+/L-)
Input filter time< 1000 µs
Input frequency0.5 kHz
Type of protectionOverload protection
Short-circuit protection for the sensor supply

Digital outputs

Output descriptionIO-Link ports in digital output (DO) mode
Connection methodM12 connector, X01 ... X04 have double occupancy
Connection technology3-wire
Number of outputsmax. 8
Nominal output voltage24 V DC
Maximum output current per channel150 mA
Maximum output current per device1.2 A
Nominal load, ohmic3.6 W (160 Ω, at nominal load)
Nominal load, inductive3.6 VA (0.8 H, 160 Ω, at nominal load)
Signal delaymax. 150 µs (when switched on)
max. 200 µs (when switched off)
Switching rate1 per second, maximum (at nominal inductive load)
Limitation of the voltage induced on circuit interruption-15 V DC
Output voltage when switched offmax. 1 V
Output current when switched offmax. 300 µA
Type of protectionOverload protection
Short-circuit protection
Behavior with overloadShutdown with automatic restart

Electrical isolation

Test section24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, IO-Link ports)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet 1)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet 2)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet 1)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports) 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min.

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.