I/O module AxiolineF, Temperature recording module, Analogue inputs: 4 (4 inputs for thermocouples or linear voltage, additionally 1 input -5 V up to +5 V), connection technology: 2 conductors (shielded, twisted in pairs), transmission speed on the local bus: 100 MBit/s, protection rating: IP20, including bus socket module and AxiolineF connectors

Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2688598
Packing unit1 pc
Catalog pagePage 119 (C-6-2017)
GTIN4046356780117
Weight per Piece (excluding packing)144.000 g
Custom tariff number85389091
Country of originDE (Germany)

Dimensions

Dimensional drawing
Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

Connection data

DesignationAxioline F connector
Connection methodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

General

Mounting typeDIN rail
Net weight144 g
Note on weight specificationswith connectors and bus base module

Interfaces

DesignationAxioline F local bus
No. of channels2
Connection methodBus base module
Transmission speed100 Mbps

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptiontyp. 112 mA
max. 160 mA
Power consumptiontyp. 0.54 W (logic)
max. 0.8 W (logic)
DesignationSupply for analog modules (UA)
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumptiontyp. 23 mA
max. 40 mA
Power consumptionmax. 0.96 W (Peripherals)
typ. 1.05 W (entire device)
max. 1.76 W (entire device)
Type of protectionSurge protection of the supply voltage
Polarity reversal protection of the supply voltage
Transient protection

Analog inputs

Number of inputs4 +1 (4 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V)
Input nameAnalog inputs
Description of the inputInputs for thermocouples or linear voltage
Connection methodSpring-cage connection with direct connector-in method
Connection technology2-wire (shielded, twisted pair)
Sensor types (RTD) that can be usedPt 100 (2 external cold junctions, can also be used as a sensor input)
Measuring principleSigma/Delta process
Measured value representation16 bits (15 bits + sign bit)
Resolution A/D24 bit
Type of protectionShort-circuit protection, overload protection of the inputs
Transient protection of inputs
Input filter time40 ms

Electrical isolation

Test section5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min.
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min.
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet