View larger
AXL F DOR4/2 AC/220DC 1F
2700608
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Dimensional drawing | ![]() |
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Note on application | |
| Note on application | Only for industrial use |
| Axioline F local bus | |
| Number of interfaces | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Module | |
| Input address area | 0 Byte |
| Output address area | 1 Byte |
| Required parameter data | 1 Byte |
| Required configuration data | 6 Byte |
| Relay | |
| Number of outputs | 4 (floating) |
| Connection method | Push-in connection |
| Connection technology | 2-conductor |
| Contact switching type | N/O contact |
| Switching current | max. 8 A AC (cos phi = 1) |
| For DC see load limit curve, e.g., the following values: | |
| max. 8 A DC (≤ 30 V, ohmic load) | |
| max. 500 mA DC (110 V, ohmic load) | |
| max. 250 mA DC (220 V DC, ohmic load) | |
| max. 220 mA DC (125 V DC, L/R ≤ 50 ms, applications with UL approval) | |
| max. 110 mA DC (250 V DC, L/R ≤ 50 ms, applications with UL approval) | |
| Switching capacity | max. 2000 VA |
| For DC see load limit curve, e.g., the following values: | |
| max. 240 W (30 V DC) | |
| max. 55 W (≥ 60 V DC) | |
| max. 25 W (125 V DC, 250 V DC, applications with UL approval) | |
| Switching capacity in accordance with IEC 60947-5-1 | 6 A (120 V (AC15)) |
| 3 A (240 V (AC15)) | |
| 0.22 A (125 V (DC13)) | |
| 0.1 A (250 V (DC-13)) | |
| Switching frequency | max. 6 (per minute) |
| Mechanical service life | 10x 106cycles |
| Product type | I/O component |
| Product family | Axioline F |
| Type | block modular |
| Mounting position | any (observe temperature and current derating) |
| Scope of delivery | including bus base module and Axioline F connectors |
| Data management status | |
| Article revision | 02 |
| Insulation characteristics | |
| Overvoltage category | III (EN 61010-2-201/UL 61010-2-201), up to 2000 m above sea level II (EN 61010-2-201/UL 61010-2-201), up to 3000 m above sea level |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | 1.4 W |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Current draw | max. 280 mA (all relays pick up) |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Relay contact / logic | 4 kV |
| 5 kV | |
| Test voltage: Relay contact / functional ground | 4 kV |
| 5 kV | |
| Test voltage: Relay contact/relay contact (open contact) | 1 kV, 50 Hz, 1 min. |
| Test voltage: Relay contact/relay contact (adjacent male connectors) | 2.5 kV |
| Connection technology | |
| Connection name | Axioline F connector |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Axioline F connector | |
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C (max. 6 A/channel for wall mounting on horizontal DIN rail; max. 4 A/channel for any mounting position) |
| -25 °C ... 50 °C (max. 8 A/channel for wall mounting on horizontal DIN rail; max. 6 A/channel for any mounting position) | |
| -25 °C ... 40 °C (max. 8 A/channel for any mounting position) | |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Standard designation | Ambient conditions |
| Standards/specifications | IEC 61850-3 |
| Mounting type | DIN rail mounting |
| Mounting position | any (observe temperature and current derating) |
| Feature Name | Feature Value |
|---|---|
| Voltage type (supply voltage) (EF002991) | DC |
| Number of digital inputs (EF001992) | 0 |
| Number of digital outputs (EF001993) | 0 |
| Digital inputs configurable (EF008516) | No |
| Digital outputs configurable (EF008520) | No |
| Type of voltage (input voltage) (EF003033) | DC |
| Type of digital output (EF003601) | None |
| Short-circuit protection, outputs available (EF003203) | No |
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 |
| Number of interfaces PROFINET (EF006932) | 0 |
| Number of HW-interfaces RS-232 (EF003021) | 0 |
| Number of HW-interfaces RS-422 (EF003022) | 0 |
| Number of HW-interfaces RS-485 (EF003023) | 0 |
| Number of HW-interfaces serial TTY (EF003024) | 0 |
| Number of HW-interfaces parallel (EF003026) | 0 |
| Number of HW-interfaces wireless (EF006933) | 0 |
| Number of HW-interfaces USB (EF003025) | 0 |
| Number of HW-interfaces other (EF003027) | 0 |
| With optical interface (EF003028) | No |
| Radio standard Bluetooth (EF007178) | No |
| Radio standard WLAN 802.11 (EF007179) | No |
| Radio standard GPRS (EF008523) | No |
| Radio standard GSM (EF008524) | No |
| Radio standard UMTS (EF008525) | No |
| IO link master (EF007298) | No |
| System accessory (EF004118) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |
| Type of electric connection (EF003961) | Other |
| Time delay at signal change (EF002382) | 0 ms |
| Fieldbus connection over separate bus coupler possible (EF004002) | Yes |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting/direct mounting (EF007020) | No |
| Front built-in possible (EF007016) | No |
| Rack-assembly possible (EF007018) | No |
| Suitable for safety functions (EF001597) | No |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Appendant operation agent (Ex ia) (EF004141) | No |
| Appendant operation agent (Ex ib) (EF004142) | No |
| Explosion safety category for gas (EF003997) | None |
| Explosion safety category for dust (EF003998) | None |
| Width (EF000008) | 53.6 mm |
| Height (EF000040) | 125.893725 mm |
| Depth (EF000049) | 52.589698 mm |