PHOENIX CONTACT AXL F DO4/3 AC 1F AXL F DO4/3 AC 1F 2702068 PHOENIX CONTACT I/O module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL F DO4/3 AC 1F 2702068 PHOENIX CONTACT I/O module

AXL F DO4/3 AC 1F

2702068

PHOENIX CONTACT

1 Pcs.

I/O module AxiolineF, Digital output module, Digital outputs:4 (Triac outputs with zero voltage switch), 230 VAC, 2 A, connection technology:3 conductors, transmission speed on the local bus:100 MBit/s, protection index: IP20, including bus socket module and AxiolineF connectors

Automation > Fieldbus, decentr. periphery - digital I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2702068
Packing unit1 pc
Catalog pagePage 110 (C-6-2017)
GTIN4046356933087
Weight per Piece (excluding packing)239.000 g
Custom tariff number85389091
Country of originDE (Germany)

Dimensions

Dimensional drawing
Width53.6 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C (max. 2 A/channel for wall mounting on horizontal DIN rail; max. 1 A/channel for any mounting position)
-25 °C ... 50 °C (max. 2 A/channel for any mounting position)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

Connection data

DesignationAxioline F connector
Connection methodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature.
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.16
Stripping length8 mm

General

Mounting typeDIN rail
Net weight239 g
Note on weight specificationswith connectors and bus base module

Interfaces

DesignationAxioline F local bus
No. of channels2
Connection methodBus base module
Transmission speed100 Mbps

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptionmax. 120 mA
Power consumptionmax. 600 mW
DesignationSupply for digital output modules (UO)
Supply voltage230 V AC
Supply voltage range12 V AC ... 253 V AC (including all tolerances, including ripple, 50 ... 60 Hz)
Current consumptionmax. 8 A (provide external protection)
Power consumptionmax. 2024 VA (of which 8 VA internal losses)
Type of protectionSurge protection of the supply voltage
Protectionmax. 8 A

Digital outputs

Output nameDigital outputs
Connection methodPush-in connection
Connection technology3-wire
Number of outputs4 (Triac outputs with zero voltage switch)
Type of protectionExternal protection required
Output voltage230 V AC
Nominal output voltage230 V AC
Maximum output current per channel2 A AC
Maximum output current per module8 A AC (provide external protection)
Nominal load, ohmicmax. 460 W (at nominal voltage)

Electrical isolation

Test sectionI/Os / logic 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201)
I/Os / logic 5 kV Pulse test voltage according to EN 61850/IEC 61850
I/O / functional earth ground 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201)
I/O / functional earth ground 5 kV Pulse test voltage according to EN 61850/IEC 61850
I/O area AC / PE 4 kV Rated surge voltage (basic insulation according to EN 61010-2-201/IEC 61010-2-201)

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Developed according to standardIEC 61850-3 Immunity to magnetic fields, EN 61000-4-8/IEC 61000-4-8 300 A/m continuous, 1000 A/m for 1 s
IEC 61850-3 Immunity to attenuated oscillating magnetic fields, EN 61000-4-10/IEC 61000-4-10 100 A/m
IEC 61850-3 Immunity to conducted common-mode interference, EN 61000-4-16/IEC 61000-4-16 30 V continuous, 300 V for 1 s
IEC 61850-3 Attenuated oscillating waves, EN 61000-4-18/IEC 61000-4-18 1 kV symmetrical, 2.5 kV asymmetrical

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


ETIM for 2702068 PLC's (EC001599)
Feature Name Feature Value
Supply voltage AC 50 Hz (EF007532) 12 V
Supply voltage AC 60 Hz (EF007533) 12 V
Voltage type (supply voltage) (EF002991) DC
Number of digital inputs (EF001992) 0
Number of digital outputs (EF001993) 4
Digital inputs configurable (EF008516) No
Digital outputs configurable (EF008520) No
Type of voltage (input voltage) (EF003033) DC
Type of digital output (EF003601) Other
Output current (EF003202) 2 A
Permitted voltage at output (EF007553) 230 V
Short-circuit protection, outputs available (EF003203) No
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) No
Radio standard Bluetooth (EF007178) No
Radio standard WLAN 802.11 (EF007179) No
Radio standard GPRS (EF008523) No
Radio standard GSM (EF008524) No
Radio standard UMTS (EF008525) No
IO link master (EF007298) No
System accessory (EF004118) Yes
Degree of protection (IP) (EF005474) IP20
Type of electric connection (EF003961) Other
Time delay at signal change (EF002382) 0 ms
Fieldbus connection over separate bus coupler possible (EF004002) Yes
Suitable for rail mounting (EF003972) Yes
Wall mounting/direct mounting (EF007020) No
Front built-in possible (EF007016) No
Rack-assembly possible (EF007018) No
Suitable for safety functions (EF001597) No
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Appendant operation agent (Ex ia) (EF004141) No
Appendant operation agent (Ex ib) (EF004142) No
Explosion safety category for gas (EF003997) None
Explosion safety category for dust (EF003998) None
Width (EF000008) 53.6 mm
Height (EF000040) 125.893725 mm
Depth (EF000049) 52.589698 mm

Product Datasheet