PHOENIX CONTACT AXC 1050 XC AXC 1050 XC 2701295 PHOENIX CONTACT Controller View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXC 1050 XC 2701295 PHOENIX CONTACT Controller

AXC 1050 XC

2701295

PHOENIX CONTACT

1 Pcs.

Controller Axiocontrol for the Axioline direct I/O control system. With 2 Ethernet interfaces, extended temperature range and programmability in accordance with IEC 61131-3. Complete with connector and labeling surface.

Automation > PLC CPU-module
Control Systems (CST)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2701295
Packing unit1 pc
Catalog pagePage 76 (C-6-2017)
GTIN4055626000091
Weight per Piece (excluding packing)225.600 g
Custom tariff number85371091
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width45 mm
Height125.9 mm
Depth74 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C (Observe derating as per user manual)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)58 kPa ... 106 kPa (up to 4500 m above mean sea level)
Shock30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation)5g

Control system

Engineering toolPC WORX
PC WORX EXPRESS
Programming languages supportedProgramming in acc. with IEC 61131-3
Diagnostics toolDIAG+
Configuration toolConfig+ Version 1.01 or later

IEC 61131 runtime system

Engineering toolPC WORX
PC WORX EXPRESS
Program memory2 Mbyte
Mass storage2 Mbyte
Retentive mass storage48 kByte (NVRAM)
Number of control tasks8
Realtime clockYes

Fieldbus function

Amount of process datamax. 4096 Bit (Axioline F local bus (input))
max. 4096 Bit (Axioline F local bus (output))
max. 32768 Bit (internal Modbus /TCP client)
Number of supported devicesmax. 63 (per station)
Number of local bus devices that can be connectedmax. 63 (observe current consumption)

Data interfaces

InterfaceAxioline F local bus
Number1
Connection methodBus base module
Transmission speed100 Mbps
InterfaceService
Number1
Connection methodMicro USB type B
Transmission speedmax. 115.2 kbps
InterfaceEthernet
Number2
Connection methodRJ45 socket
Transmission speed10/100 Mbps

PROFINET

Device functionPROFINET controller, PROFINET device
SpecificationVersion 2.2
Update ratemin. 32 ms (16 devices)
min. 32 ms (8 devices)
min. 16 ms (4 devices)
min. 8 ms (2 devices)
min. 4 ms (1st device)

Power supply

Typical current consumption125 mA
Max. current consumption160 mA
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC
Residual ripple± 5 %
Power dissipationmax. 3 W

Mechanical design

Weight225.6 g
Diagnostics displayNo
Controller redundancyNo
Safety functionNo

General data

ProcessorAltera Nios II 1x 100 MHz

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Interference emissionNoise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class B
Immunity to surgeNoise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV
Immunity to burstNoise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
Immunity to EFNoise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity to ESDNoise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity to conducted interferenceNoise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V
Vibration (storage/transport)5g
Shock30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation)5g
Shock (operation)10g (Bump endurance test according to DIN EN 60068-2-27)

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2701295 PLC's (EC000236)
Feature Name Feature Value
Supply voltage DC (EF007534) 19.2 V
Voltage type (supply voltage) (EF002991) DC
Model (EF000010) Modular
Processing time (1K, binary operation) (EF003004) 0.0013 ms
Number of HW-interfaces industrial Ethernet (EF003020) 2
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces USB (EF003025) 1
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces other (EF003027) 1
Number of analogue outputs (EF001995) 0
Number of analogue inputs (EF001994) 0
Number of digital inputs (EF001992) 0
Number of digital outputs (EF001993) 0
With optical interface (EF003028) No
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for EtherCAT (EF017564) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) Yes
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) No
IO link master (EF007298) No
System accessory (EF004118) Yes
Redundancy (EF003156) Yes
Type of memory (EF002996) NVRAM
Memory size (EF002997) 2048 kByte
Additional program memory possible (EF003029) Yes
Suitable for rail mounting (EF003972) Yes
Wall mounting/direct mounting (EF007020) No
Front built-in possible (EF007016) No
Rack-assembly possible (EF007018) No
Suitable for safety functions (EF001597) No
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Appendant operation agent (Ex ia) (EF004141) No
Appendant operation agent (Ex ib) (EF004142) No
Explosion safety category for gas (EF003997) None
Explosion safety category for dust (EF003998) None
Width (EF000008) 45 mm
Height (EF000040) 125.893514 mm
Depth (EF000049) 74.83586 mm