View larger
MINI MCR-2-UI-UI
2902037
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
The 3-way signal conditioner with plug-in connection technology and calibrated measuring range changeover can be configured using DIP switches and is used for the electrical isolation, conversion, amplification, and filtering of unipolar and bipolar standard and normalized signals. On the input side, the standard analog signals 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V, 0 ... 5 V, 1 ... 5 V or -10 ... 10 V, and signals2 ... 10 V, 0 ... 20 V, 4 ... 20 V, 0 ... 24 V, 0 ... 30 V, -5 ... 5 V, -20 ... 20 V, -24 ... 24 V, -30 ... 30 V and -20 ... 20 mA are available. On the output side, 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V, 0 ... 5 V, 1 ... 5 V, -10 ... 10 V and -5 ... 5 V are possible. There is no need for adjustment following a measuring range changeover. The measuring transducer supports fault monitoring and NFC communication.
| Width | 6.2 mm |
|---|---|
| Height | 110.5 mm |
| Depth | 120.5 mm |
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Degree of protection | IP20 |
| Number of inputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Voltage input signal | 0 V ... 5 V (via DIP switch) |
| 1 V ... 5 V (via DIP switch) | |
| -5 V ... 5 V (via DIP switch) | |
| 0 V ... 10 V (via DIP switch) | |
| 2 V ... 10 V (via DIP switch) | |
| -10 V ... 10 V (via DIP switch) | |
| 0 V ... 20 V (via DIP switch) | |
| 4 V ... 20 V (via DIP switch) | |
| -20 V ... 20 V (via DIP switch) | |
| 0 V ... 24 V (via DIP switch) | |
| 4.8 V ... 24 V (via DIP switch) | |
| -24 V ... 24 V (via DIP switch) | |
| 0 V ... 30 V (via DIP switch) | |
| 6 V ... 30 V (via DIP switch) | |
| -30 V ... 30 V (via DIP switch) | |
| Current input signal | 0 mA ... 20 mA (via DIP switch) |
| 4 mA ... 20 mA (via DIP switch) | |
| -20 mA ... 20 mA (via DIP switch) | |
| Max. input voltage | 33 V |
| Max. input current | 24 mA |
| Input resistance of voltage input | > 1000 kΩ |
| Input resistance current input | approx. 63 Ω |
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Voltage output signal | 0 V ... 5 V (via DIP switch) |
| 1 V ... 5 V (via DIP switch) | |
| -5 V ... 5 V (via DIP switch) | |
| 0 V ... 10 V (via DIP switch) | |
| 2 V ... 10 V (via DIP switch) | |
| -10 V ... 10 V (via DIP switch) | |
| Current output signal | 0 mA ... 20 mA (via DIP switch) |
| 4 mA ... 20 mA (via DIP switch) | |
| Max. output current | 22 mA |
| Short-circuit current | < 32 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | ≤ 600 Ω (at 20 mA) |
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Typical current consumption | 25 mA (Current output, at 24 V DC incl. load) |
| 54 mA (Current output, at 12 V DC incl. load) | |
| Power consumption | ≤ 800 mW (at IOUT= 20 mA, 9.6 V DC, 600 Ω load) |
| Connection method | Screw connection |
|---|---|
| Single conductor/terminal point, solid, with ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, with ferrule, max. | 1.5 mm² |
| Single conductor/terminal point, solid, without ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, without ferrule, max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Min. AWG conductor cross section, flexible | 24 |
| Max. AWG conductor cross section, flexible | 12 |
| Stripping length | 10 mm |
| Screw thread | M3 |
| No. of channels | 1 |
|---|---|
| Maximum transmission error | ≤ 0.1 % (of final value) |
| ≤ 0.15 % (of final value, at IN: 4 ... 20 mA / OUT: -10 V ... 10 V) | |
| Maximum temperature coefficient | 0.01 %/K |
| Limit frequency (3 dB) | 30 Hz (via DIP switch) |
| 5 kHz (via DIP switch) | |
| Step response (10-90%) | < 8.5 ms (with 30 Hz filter) |
| Protective circuit | Transient protection |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Overvoltage category | II |
| Pollution degree | 2 |
| Rated insulation voltage | 300 V (effective) |
| Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | gray |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | Ex II 3 G Ex nA IIC T4 Gc X |
| UL, USA / Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| Certificate of classification | DNV GL 14445-15HH |
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Feature Name | Feature Value |
|---|---|
| Type of power supply (EF001469) | Other |
| Rated supply voltage DC (EF007078) | 9.6 V |
| Number of input ranges -60 mV ... +60 mV (EF006927) | 0 |
| Number of input ranges -100 mV ... +100 mV (EF006912) | 0 |
| Number of input ranges -300 mV ... +300 mV (EF006920) | 0 |
| Number of input ranges -500 mV ... +500 mV (EF006926) | 0 |
| Number of input ranges -1 V ... +1 V (EF006906) | 0 |
| Number of input ranges -2 V ... +2 V (EF006913) | 0 |
| Number of input ranges -2.5 V ... +2.5 V (EF006915) | 0 |
| Number of input ranges -5 V ... +5 V (EF006923) | 1 |
| Number of input ranges -10 V ... +10 V (EF006909) | 1 |
| Number of input ranges -20 V ... +20 V (EF006917) | 1 |
| Number of input ranges 0 mV ... 60 mV (EF006905) | 0 |
| Number of input ranges 0 mV ... 100 mV (EF006893) | 0 |
| Number of input ranges 0 mV ... 200 mV (EF006898) | 0 |
| Number of input ranges 0 mV ... 300 mV (EF006901) | 0 |
| Number of input ranges 0 mV ... 500 mV (EF006904) | 0 |
| Number of input ranges 0 V ... 1 V (EF006890) | 0 |
| Number of input ranges 0 V ... 2 V (EF006894) | 0 |
| Number of input ranges 0 V ... 2.5 V (EF006895) | 0 |
| Number of input ranges 0 V ... 5 V (EF006903) | 1 |
| Number of input ranges 0 V ... 10 V (EF006892) | 1 |
| Number of input ranges 0 V ... 20 V (EF006897) | 1 |
| Number of input ranges 0 V ... 24 V (EF006899) | 1 |
| Number of input ranges 0 V ... 30 V (EF006900) | 1 |
| Number of input ranges 1 V ... 5 V (EF006907) | 1 |
| Number of input ranges 2 V ... 10 V (EF006914) | 1 |
| Number of input ranges +5 V ... -5 V (EF006889) | 0 |
| Number of input ranges +10 V ... -10 V (EF006888) | 0 |
| Number of input ranges 5 V ... 0 V (EF006924) | 0 |
| Number of input ranges 5 V ... 1 V (EF006925) | 0 |
| Number of input ranges 10 V ... 0 V (EF006910) | 0 |
| Number of input ranges 10 V ... 2 V (EF006911) | 0 |
| Number of input ranges 0 mA ... 5 mA (EF006902) | 0 |
| Number of input ranges 0 mA ... 10 mA (EF006891) | 0 |
| Number of input ranges 0 mA ... 20 mA (EF006896) | 1 |
| Number of input ranges 4 mA ... 20 mA (EF006921) | 1 |
| Number of input ranges -5 mA ... +5 mA (EF006922) | 0 |
| Number of input ranges -10 mA ... +10 mA (EF006908) | 0 |
| Number of input ranges -20 mA ... +20 mA (EF006916) | 1 |
| Number of input ranges 20 mA ... 0 mA (EF006918) | 0 |
| Number of input ranges 20 mA ... 4 mA (EF006919) | 0 |
| Number of output ranges -60 mV ... +60 mV (EF006880) | 0 |
| Number of output ranges -100 mV ... +100 mV (EF006865) | 0 |
| Number of output ranges -300 mV ... +300 mV (EF006873) | 0 |
| Number of output ranges -500 mV ... +500 mV (EF006879) | 0 |
| Number of output ranges -1 V ... +1 V (EF006859) | 0 |
| Number of output ranges -2 V ... +2 V (EF006866) | 0 |
| Number of output ranges -2.5 V ... +2.5 V (EF006868) | 0 |
| Number of output ranges -5 V ... +5 V (EF006876) | 1 |
| Number of output ranges -10 V ... +10 V (EF006862) | 1 |
| Number of output ranges -20 V ... +20 V (EF006870) | 0 |
| Number of output ranges 0 mV ... 60 mV (EF006858) | 0 |
| Number of output ranges 0 mV ... 100 mV (EF006846) | 0 |
| Number of output ranges 0 mV ... 200 mV (EF006851) | 0 |
| Number of output ranges 0 mV ... 300 mV (EF006854) | 0 |
| Number of output ranges 0 mV ... 500 mV (EF006857) | 0 |
| Number of output ranges 0 V ... 1 V (EF006843) | 0 |
| Number of output ranges 0 V ... 2 V (EF006847) | 0 |
| Number of output ranges 0 V ... 2.5 V (EF006848) | 0 |
| Number of output ranges 0 V ... 5 V (EF006856) | 1 |
| Number of output ranges 0 V ... 10 V (EF006845) | 1 |
| Number of output ranges 0 V ... 20 V (EF006850) | 0 |
| Number of output ranges 0 V ... 24 V (EF006852) | 0 |
| Number of output ranges 0 V ... 30 V (EF006853) | 0 |
| Number of output ranges 1 V ... 5 V (EF006860) | 1 |
| Number of output ranges 2 V ... 10 V (EF006867) | 1 |
| Number of output ranges +5 V ... -5 V (EF006842) | 0 |
| Number of output ranges +10 V ... -10 V (EF006841) | 0 |
| Number of output ranges 5 V ... 0 V (EF006877) | 0 |
| Number of output ranges 5 V ... 1 V (EF006878) | 0 |
| Number of output ranges 10 V ... 0 V (EF006863) | 0 |
| Number of output ranges 10 V ... 2 V (EF006864) | 0 |
| Number of output ranges 0 mA ... 5 mA (EF006855) | 0 |
| Number of output ranges 0 mA ... 10 mA (EF006844) | 0 |
| Number of output ranges 0 mA ... 20 mA (EF006849) | 1 |
| Number of output ranges 4 mA ... 20 mA (EF006874) | 1 |
| Number of output ranges -5 mA ... +5 mA (EF006875) | 0 |
| Number of output ranges -10 mA ... +10 mA (EF006861) | 0 |
| Number of output ranges -20 mA ... +20 mA (EF006869) | 0 |
| Number of output ranges 20 mA ... 0 mA (EF006871) | 0 |
| Number of output ranges 20 mA ... 4 mA (EF006872) | 0 |
| Number of channels (EF000259) | 1 |
| Malfunction message output (EF007499) | Yes |
| Inherently safe according to EN 60947-5-6 NAMUR (EF007112) | No |
| Galvanic separation between inputs (EF007224) | No |
| SIL according to IEC 61508 (EF009889) | None |
| Height (EF000040) | 109.81 mm |
| Width (EF000008) | 6.2 mm |
| Depth (EF000049) | 119.2 mm |
| Power consumption (EF000346) | 0.8 W |
| Load (EF007096) | 600 Ohm |
| Operating temperature (EF002393) | -40 °C |
| Temperature drift (EF007507) | 0.01 %/K |
| Construction type of device (EF007276) | Built-in device |
| Type of electric connection (EF003961) | Screw connection |
| Mounting method (EF000003) | Snap mounting support rail |
| Degree of protection (IP) (EF005474) | IP20 |