PHOENIX CONTACT ELR H3-IES-SC-24DC/500AC-0,6 ELR H3-IES-SC- 24DC/500AC-0,6 2900566 PHOENIX CONTACT Hybrid motor starter for starting 3~ AC motors up to 5.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

ELR H3-IES-SC- 24DC/500AC-0,6 2900566 PHOENIX CONTACT Hybrid motor starter for starting 3~ AC motors up to 5..

ELR H3-IES-SC-24DC/500AC-0,6

2900566

PHOENIX CONTACT

1 Pcs.

Hybrid motor starter for starting 3~ AC motors up to 500 V AC and 0.6 A output current, with 24 V DC control voltage, adjustable overload shutdown and emergency stop function to SIL3 /PL e, and screw connection. Hybrid start controller for starting 3~ AC motors up to 500 V AC and 0.6 A output current, with a control voltage of 24 V DC, adjustable overload circuit breaker, emergency stop function up to SIL 3/PL e and screw connection.

Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Input data

Input nameDevice supply
Rated control circuit supply voltage US24 V DC
Rated control supply current IS40 mA
Protective circuitProtection against polarity reversal Parallel polarity protection diode
Surge protection
Operating voltage displayGreen LED
Status displayYellow LED
IndicationRed LED
Input nameControl input right/left
Rated actuating voltage UC24 V DC
Rated actuating current IC5 mA
Switching threshold9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Protective circuitProtection against polarity reversal
Typical turn-off time< 30 ms

Output data load output

Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Load current range75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947Class 10A
Rated operating current at AC-510.6 A
Rated operating current at AC-53a0.6 A
Leakage current0 mA
Protective circuitSurge protection Varistor

Output data reply output

NoteConfirmation: floating change-over contact, signal contact
Contact type1 PDT

Connection data, control circuit

Connection nameControl circuits
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Torque0.5 Nm ... 0.6 Nm

General

Switching frequency≤ 2 Hz (Load-dependent)
Mounting positionvertical (horizontal DIN rail, motor output below)
Assembly instructionsalignable, for spacing see derating
Operating mode100% operating factor
DesignationStandards/regulations
Standards/regulationsIEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Safety Integrity Level according to IEC 61508SIL 3 (safe shutdown)
SIL 2 (motor protection)
Category acc. to EN ISO 138493 (Safe shutdown)
Performance level according to ISO 13849e (Safe shutdown)

Dimensions

Width22.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Degree of protectionIP20

ETIM for 2900566 Low-voltage industrial controls and switchgear (EC001037)
Feature Name Feature Value
Type of motor starter (EF009598) Direct starter
With short-circuit release (EF006691) No
Rated control supply voltage DC (EF003980) 19.2 V
Voltage type for actuating (EF008242) DC
Rated operation current Ie (EF001443) 0.6 A
Rated operation current at AC-3, 400 V (EF009602) 0.6 A
Overload release current setting (EF002336) 0.075 A
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Temperature compensated overload protection (EF009604) No
Release class (EF006668) CLASS 10
Type of electrical connection of main circuit (EF006819) Screw connection
Type of electrical connection for auxiliary- and control current circuit (EF006979) Screw connection
Suitable for rail mounting (EF003972) Yes
Number of command positions (EF001372) 1
Suitable for emergency stop (EF001433) Yes
External reset possible (EF003426) Yes
Degree of protection (IP) (EF005474) IP20
Width (EF000008) 22.5 mm
Height (EF000040) 107 mm
Depth (EF000049) 114 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.