PHOENIX CONTACT VAL-US-600D/30-P VAL-US-600D/30-P 2910341 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-US-600D/30-P 2910341 PHOENIX CONTACT Type 2 surge protection plug

VAL-US-600D/30-P

2910341

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Type 1 surge protection device, UL recognized component, and IEC Type 2 plug-in surge protection with varistor and thermal disconnect device for use with VAL-US base elements, mechanical and optical fault signaling

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact part VAL-US-600D/30-P functions as a Type 2 surge protection plug configured to handle specific DC voltage environments within industrial installations. Such protective modules safeguard sensitive photovoltaic or industrial power systems by shunting high-magnitude voltage transients to ground. Specific pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2910341
  • Packing unit: 1 pc
  • Note: Made to Order (non-returnable)
  • GTIN: 4055626444833
  • Weight per Piece (excluding packing): 60.000 g
  • Custom tariff number: 85363030
  • Country of origin: US (United States)
  • Height: 52.4 mm
  • Width: 17.5 mm
  • Depth: 55.3 mm
  • Horizontal pitch: 1 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Altitude: ≤ 2000 m (amsl (above mean sea level))
  • Permissible humidity (operation): 5 % ... 95 %

More info

▲

Key Commercial Data

Orderkey2910341
Packing unit1 pc
NoteMade to Order (non-returnable)
GTIN4055626444833
Weight per Piece (excluding packing)60.000 g
Custom tariff number85363030
Country of originUS (United States)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
Mode of protectionL-L
L-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN554/960 V AC (TN)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC750 V AC
Residual current IPE≤ 500 µA
Standby power consumption PC≤ 400 mVA
Nominal discharge current In(8/20) µs15 kA
Maximum discharge current Imax(8/20) µs30 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.9 kV
Residual voltage Ures≤ 2.9 kV (at In)
≤ 2.7 kV (at 10 kA)
≤ 2.5 kV (at 5 kA)
≤ 2.3 kV (at 3 kA)
TOV behavior at UT1000 V AC (5 s / withstand mode)
1056 V AC (120 min / safe failure mode)
Max. backup fuse with branch wiring100 A (gG)

Connection data

Connection methodVALVETRAB plug-in system

UL specifications

SPD Type1CA
Maximum continuous operating voltage MCOV750 V AC
Nom. voltage600 V AC (Delta)
Mode of protectionL-L
L-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Voltage protection rating VPR2500 V
Nominal discharge current In20 kA
Maximum Surge Current per Phase30 kA
Short-circuit current rating (SCCR)200 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.