View larger
VAL-US 60/1+1/1U/FM 2909630 PHOENIX CONTACT Type 2 surge arrester
VAL-US 60/1+1/1U/FM
2909630
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact VAL-US 60/1+1/1U/FM type 2 surge arrester protects low-voltage electrical circuits from transient overvoltages and grid switching disturbances. Integrated remote signaling contacts allow maintenance personnel to monitor device status remotely.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): No
- System configuration IT (EF009927): No
- System configuration TN (EF009928): No
- System configuration TN-C (EF009929): No
- System configuration TN-C-S (EF009933): No
- System configuration TN-S (EF009930): Yes
- System configuration TT (EF009931): No
- System configuration other (EF009932): No
- Nominal discharge surge current (8/20) (EF004214): 15 kA
- Max. discharge surge current (8/20) (EF012274): 40 kA
- Max. continuous voltage AC (EF004198): 75 V
- Voltage protection level L-N (EF004236): 0.55 kV
- Short-circuit breaking capacity (Isccr) (EF012627): 25 kA
- Integrated backup fuse (EF008797): Yes
- Leakage-current free (EF016002): No
- With remote signalling contact (EF000422): Yes
More info
▲Key Commercial Data
| Orderkey | 2909630 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4055626370538 |
| Weight per Piece (excluding packing) | 222.220 g |
| Custom tariff number | 85363010 |
| Country of origin | US (United States) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-S |
| Mode of protection | L-N |
| N-PE | |
| Mounting type | Panel mount |
| Color | gray |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Additional descriptions
| Note | For installation into a touch protected cabinet. For applications with UC> 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts. |
|---|
Protective circuit
| Nominal voltage UN | -48 V DC ±10 % (RRH) |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 75 V AC |
| 100 V DC | |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 0.45 mA |
| Standby power consumption PC | ≤ 35 mVA |
| Nominal discharge current In(8/20) µs | 15 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 0.55 kV |
| Residual voltage Ures | ≤ 0.55 kV (at In) |
| ≤ 0.425 kV (at 10 kA) | |
| ≤ 0.325 kV (at 5 kA) | |
| ≤ 0.275 kV (at 3 kA) | |
| TOV behavior at UT | 100 V AC (5 s / withstand mode) |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 80 A AC (gG - 16 mm²) |
| Max. backup fuse with branch wiring | 160 A AC (gG) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC |
| 125 V AC (UL) | |
| 125 V DC (200 mA DC) | |
| Operating current | 5 mA AC ... 1.5 A |
| 1 A (UL) | |
| 1 A (30 V DC) | |
| Connection method | Push-in spring connection |
| Stripping length | 6 mm |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 0.5 mm² |
| Conductor cross section solid min. | 0.14 mm² |
| Conductor cross section solid max. | 0.5 mm² |
| Conductor cross section AWG | 24 ... 20 (UL) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 2.5 Nm ... 3 Nm |
| 22 lbf-in. ... 26.5 lbf-in. (UL) | |
| Stripping length | 16 mm |
| Conductor cross section flexible min. | 1.5 mm² |
| Conductor cross section flexible max. | 25 mm² |
| Conductor cross section solid min. | 1.5 mm² |
| Conductor cross section solid max. | 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| 10 ... 2 (UL) |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 75 V AC |
| 100 V DC | |
| Nominal voltage | 60 V DC |
| Mode of protection | N-G |
| L-N | |
| (L+) - (L-) | |
| (L+) - G | |
| (L-) - G |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Conductor cross section AWG | 30 ... 14 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |