View larger
VAL-US-48/40/1+1V-FM 2910344 PHOENIX CONTACT Type 2 surge protection device
VAL-US-48/40/1+1V-FM
2910344
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protect sensitive automation infrastructure against electrical transients with the Phoenix Contact VAL-US-48/40/1+1V-FM surge protection device. Surge protection units of this class are deployed within control panels and distribution enclosures to limit sudden voltage surges and prevent costly operational downtime caused by lightning or grid switching.
Please note that pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): No
- Nominal discharge surge current (8/20) (EF004214): 15 kA
- Max. continuous voltage AC (EF004198): 100 V
- Short-circuit breaking capacity (Isccr) (EF012627): 5 kA
- Integrated backup fuse (EF008797): Yes
- Leakage-current free (EF016002): No
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- With remote signalling contact (EF000422): Yes
- Signalling at the device (EF004241): Optic
- Category type 2 (EF004230): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2910344 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626444864 |
| Weight per Piece (excluding packing) | 190.000 g |
| Custom tariff number | 85363030 |
| Country of origin | US (United States) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 60 V DC ±10 % |
|---|---|
| -48 V DC ±10 % (RRH) | |
| Maximum continuous voltage UC | 100 V DC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 0.45 mA |
| Nominal discharge current In(8/20) µs | 15 kA |
| Short-circuit current rating ISCCR | 5 kA |
| Voltage protection level Up(DC+) - (DC-) | ≤ 0.55 kV |
| Voltage protection level Up(DC+/DC-) - PE | ≤ 0.55 kV |
| Residual voltage Ures | ≤ 0.55 kV (at In) |
| ≤ 0.425 kV (at 10 kA) | |
| ≤ 0.325 kV (at 5 kA) | |
| ≤ 0.275 kV (at 3 kA) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
| Max. backup fuse with branch wiring | 125 A (gG) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC |
| 30 V DC | |
| Operating current | 5 mA AC ... 1.5 A AC |
| 1 A DC | |
| Connection method | Screw connection |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
UL specifications
| SPD Type | 4CA |
|---|---|
| Nominal voltage | 60 V DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+) - G | |
| Power distribution system | DC |
| Nominal discharge current In | 20 kA |
| Maximum Surge Current per Phase | 40 kA |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Tightening torque | 2 lbf-in. ... 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |