PHOENIX CONTACT VAL-US-240D/40/2+0-FM VAL-US-240D/40/2+0-FM 2910369 PHOENIX CONTACT Type 2 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-US-240D/40/2+0-FM 2910369 PHOENIX CONTACT Type 2 surge protection device

VAL-US-240D/40/2+0-FM

2910369

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection device 2-channel surge protection device with remote indication contact, for 240 V AC vertex delta-to-ground configurations.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact VAL-US-240D/40/2+0-FM type 2 surge protection device defends commercial and industrial power distribution networks from damaging electrical surges and transient overvoltages. Protective components of this class are installed downstream from primary protection to limit residual voltage levels.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • System configuration DC (EF009926): No
  • System configuration IT (EF009927): No
  • System configuration TN (EF009928): No
  • System configuration TN-C (EF009929): Yes
  • System configuration TN-C-S (EF009933): No
  • System configuration TN-S (EF009930): No
  • System configuration TT (EF009931): No
  • System configuration other (EF009932): No
  • Nominal discharge surge current (8/20) (EF004214): 20 kA
  • Max. discharge surge current (8/20) (EF012274): 40 kA
  • Max. continuous voltage AC (EF004198): 275 V
  • Voltage protection level L-N (EF004236): 1.35 kV
  • Short-circuit breaking capacity (Isccr) (EF012627): 25 kA
  • Integrated backup fuse (EF008797): Yes
  • Leakage-current free (EF016002): No
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm

More info

▲

Key Commercial Data

Orderkey2910369
Packing unit1 pc
NoteMade to Order (non-returnable)
GTIN4055626445083
Weight per Piece (excluding packing)213.000 g
Custom tariff number85363030
Country of originUS (United States)

Dimensions

Height96.8 mm
Width35.6 mm
Depth65.5 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-C
IT
Mode of protectionL-PEN
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Additional descriptions

NoteAdditional information for IT systems

Protective circuit

Nominal voltage UN240 V AC (IT)
240/415 V AC (TN-C)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC275 V AC
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.35 kV
Residual voltage Ures≤ 1.35 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
TOV behavior at UT335 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 750 mA AC
1 A DC
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

UL specifications

SPD Type1
Maximum continuous operating voltage MCOV (L-L)550 V
Maximum continuous operating voltage MCOV (L-G)275 V AC
Nom. voltage240 V AC (3-phase corner-grounded Delta)
Mode of protectionL-L
L-G
Power distribution systemDelta
Nominal frequency50/60 Hz
Voltage protection rating VPR (L-L)1800 V
Voltage protection rating VPR (L-G)1000 V
Nominal discharge current In20 kA
Maximum Surge Current per Phase40 kA
Short-circuit current rating (SCCR)200 kA

UL indicator/remote signaling

Operating voltage125 V AC
Operating current1 A AC
Tightening torque2 lbf-in. ... 4 lbf-in.
Conductor cross section AWG30 ... 14

UL connection data

Conductor cross section AWG10 ... 2
Tightening torque30 lbf-in.

Standards and Regulations

Standards/regulationsIEC 61643-11 2011