View larger
VAL-US-120/65/1+1-FM 2910356 PHOENIX CONTACT Type 1/2 surge protection device
VAL-US-120/65/1+1-FM
2910356
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact VAL-US-120/65/1+1-FM type 1/2 surge protection device provides comprehensive defense against severe electrical surges and direct lightning strikes in commercial settings. Industrial power distribution systems depend on hybrid protective devices of this standard to maintain uninterrupted facility safety.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): No
- System configuration IT (EF009927): No
- System configuration TN (EF009928): No
- System configuration TN-C (EF009929): No
- System configuration TN-C-S (EF009933): No
- System configuration TN-S (EF009930): Yes
- System configuration TT (EF009931): No
- System configuration other (EF009932): No
- Nominal discharge surge current (8/20) (EF004214): 12.5 kA
- Max. continuous voltage AC (EF004198): 175 V
- Voltage protection level (EF003525): 2 kV
- Voltage protection level L-N (EF004236): 0.8 kV
- Voltage protection level N-PE (EF008796): 1.7 kV
- Short-circuit breaking capacity (Isccr) (EF012627): 25 kA
- Integrated backup fuse (EF008797): Yes
- Leakage-current free (EF016002): No
More info
▲Key Commercial Data
| Orderkey | 2910356 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626444963 |
| Weight per Piece (excluding packing) | 277.000 g |
| Custom tariff number | 85363030 |
| Country of origin | US (United States) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | I / II |
|---|---|
| T1 / T2 | |
| EN type | T1 / T2 |
| IEC power supply system | TN-S |
| TT | |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 120 V AC (TN-S) |
|---|---|
| 120 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 175 V AC |
| Maximum continuous voltage UC(N-PE) | 264 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (L-N) | 12.5 kA |
| Nominal discharge current In(8/20) µs (L-PE) | 12.5 kA |
| Nominal discharge current In(8/20) µs (N-PE) | 50 kA |
| Total discharge current Itotal(10/350) µs | 25 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A (264 V AC) |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up(L-N) | ≤ 0.8 kV |
| Voltage protection level Up(L-PE) | ≤ 2 kV |
| Voltage protection level Up(N-PE) | ≤ 1.7 kV |
| Residual voltage Ures(L-N) | ≤ 0.8 kV (at In) |
| ≤ 0.75 kV (at 10 kA) | |
| ≤ 0.65 kV (at 5 kA) | |
| ≤ 0.6 kV (at 3 kA) | |
| Residual voltage Ures(L-PE) | ≤ 2 kV (at In) |
| ≤ 1.5 kV (at 10 kA) | |
| ≤ 1.4 kV (at 5 kA) | |
| ≤ 1.3 kV (at 3 kA) | |
| Residual voltage Ures(N-PE) | ≤ 0.6 kV (at In) |
| ≤ 0.5 kV (at 10 kA) | |
| ≤ 0.5 kV (at 5 kA) | |
| ≤ 0.4 kV (at 3 kA) | |
| TOV behavior at UT(L-N) | 208 V AC (5 s / withstand mode) |
| 240 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
| Max. backup fuse with branch wiring | 160 A (gG) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC |
| 30 V DC | |
| Operating current | 5 mA AC ... 1.5 A AC |
| 1 A DC | |
| Connection method | Screw connection |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
UL specifications
| SPD Type | 1 |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 175 V AC |
| Maximum continuous operating voltage MCOV (L-G) | 175 V AC |
| Maximum continuous operating voltage MCOV (N-G) | 264 V AC |
| Nom. voltage | 120 V AC |
| Mode of protection | L-N |
| L-G | |
| N-G | |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Voltage protection rating VPR (L-N) | 700 V |
| Voltage protection rating VPR (L-G) | 1500 V |
| Voltage protection rating VPR (N-G) | 1200 V |
| Nominal discharge current In | 20 kA |
| Maximum Surge Current per Phase | 65 kA |
| Short-circuit current rating (SCCR) | 200 kA |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Tightening torque | 2 lbf-in. ... 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |