View larger
VAL-SEC-T2-440-P 2909969 PHOENIX CONTACT Type 2 surge protection plug
VAL-SEC-T2-440-P
2909969
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for demanding electrical supply systems, the Phoenix Contact VAL-SEC-T2-440-P (2909969) serves as a Type 2 surge protection plug. Panel builders integrate these robust protective components into industrial power distribution networks to safeguard equipment against medium-level voltage spikes. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2909969
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 45 (C-4-2017)
- GTIN: 4055626409061
- Weight per Piece (excluding packing): 63.420 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 46.4 mm
- Width: 11.7 mm
- Depth: 59.4 mm
- Horizontal pitch: 0.6 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
More info
▲Key Commercial Data
| Orderkey | 2909969 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 45 (C-4-2017) |
| GTIN | 4055626409061 |
| Weight per Piece (excluding packing) | 63.420 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| TT | |
| Mode of protection | L-N |
| L-PEN | |
| Mounting type | on base element |
| Color | light grey RAL 7035 |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 1 |
| Surge protection fault message | optical |
Additional descriptions
| Note | Usable in all low-voltage systems between L-N or L-PEN. Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a) |
|---|
Protective circuit
| Nominal voltage UN | 400 V AC (TN) |
|---|---|
| 400 V AC (TT) | |
| 400 V AC (IT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 440 V AC |
| Standby power consumption PC | ≤ 180 mVA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA (in case of 315 A gG backup fuse) |
| 50 kA (in case of 200 A gG backup fuse) | |
| Voltage protection level Up | ≤ 1.9 kV |
| Residual voltage Ures | ≤ 1.9 kV (at In) |
| ≤ 1.65 kV (at 10 kA) | |
| ≤ 1.5 kV (at 5 kA) | |
| ≤ 1.45 kV (at 4 kA) | |
| ≤ 1.35 kV (at 2 kA) | |
| TOV behavior at UT | 581 V AC (5 s / withstand mode) |
| 762 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | 315 A (gG) |