View larger
VAL-SEC-T2-3S-350/40 2909637 PHOENIX CONTACT Type 2 surge arrester
VAL-SEC-T2-3S-350/40
2909637
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
VAL-SEC-T2-3S-350/40 2909637 Phoenix Contact type 2 surge arrester is designed to protect industrial machinery and electrical distribution infrastructure from harmful transient overvoltages. These protective units are standard additions to control cabinets, intercepting electrical spikes before they reach sensitive hardware. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2909637
- Packing unit: 1 pc
- Catalog page: Page 45 (C-4-2017)
- GTIN: 4055626378220
- Weight per Piece (excluding packing): 368.230 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 89.9 mm
- Width: 49.2 mm
- Depth: 74.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 2.7 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 2909637 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 45 (C-4-2017) |
| GTIN | 4055626378220 |
| Weight per Piece (excluding packing) | 368.230 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-S |
| TT | |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | light grey RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 4 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 240/415 V AC (TN-S) |
|---|---|
| 240/415 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 350 V AC |
| Maximum continuous operating voltage UC(L-PE) | 350 V AC |
| Maximum continuous voltage UC(N-PE) | 264 V AC |
| Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
| 63 A (TWIN ferrule 2 x 10 mm²) | |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (L-N) | 20 kA |
| Nominal discharge current In(8/20) µs (L-PE) | 20 kA |
| Nominal discharge current In(8/20) µs (N-PE) | 40 kA |
| Maximum discharge current Imax(8/20) µs (L-N) | 40 kA |
| Maximum discharge current Imax(8/20) µs (L-PE) | 40 kA |
| Maximum discharge current Imax(8/20) µs (N-PE) | 80 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A (264 V AC) |
| Short-circuit current rating ISCCR | 25 kA (in case of 315 A gG backup fuse) |
| 50 kA (in case of 200 A gG backup fuse) | |
| Voltage protection level Up(L-N) | ≤ 1.5 kV |
| Voltage protection level Up(L-PE) | ≤ 1.9 kV |
| Voltage protection level Up(N-PE) | ≤ 1.5 kV |
| Residual voltage Ures(L-N) | ≤ 1.5 kV (at In) |
| ≤ 1.3 kV (at 10 kA) | |
| ≤ 1.2 kV (at 5 kA) | |
| ≤ 1.1 kV (at 4 kA) | |
| ≤ 1 kV (at 2 kA) | |
| Residual voltage Ures(N-PE) | ≤ 0.7 kV (at In) |
| ≤ 0.7 kV (at 20 kA) | |
| ≤ 0.7 kV (at 8 kA) | |
| ≤ 0.7 kV (at 4 kA) | |
| TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
| 457 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
| 63 A (gG / TWIN ferrule 2x 10mm²) | |
| Max. backup fuse with branch wiring | 315 A (gG) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section solid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 6 mm² |