View larger
VAL-SEC-T2-2+F-120DC-FM 1033788 PHOENIX CONTACT Svodič přepětí typu 2
VAL-SEC-T2-2+F-120DC-FM
1033788
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
VAL-SEC-T2-2+F-120DC-FM 1033788 Phoenix Contact svodič přepětí typu 2 is an essential protective component engineered to safeguard electrical installations and sensitive machinery from damaging voltage spikes. Typically integrated into industrial distribution boards, this device intercepts transient surges and directs excess energy safely to the ground network. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1033788
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- GTIN: 4055626539973
- Weight per Piece (excluding packing): 287.570 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 97.9 mm
- Width: 37.3 mm
- Depth: 74.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 2 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 6000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 1033788 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4055626539973 |
| Weight per Piece (excluding packing) | 287.570 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 6000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | light grey RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 100 V DC ... 120 V DC |
|---|---|
| Maximum continuous voltage UC | 150 V DC |
| Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
| 63 A (TWIN ferrule 2 x 10 mm²) | |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Total discharge current Itotal(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 0.2 kA (without backup fuse) |
| 6 kA (for 20 A gG/B backup fuse) | |
| Voltage protection level Up(DC+) - (DC-) | ≤ 1.8 kV |
| Voltage protection level Up(DC+/DC-) - PE | ≤ 1.3 kV |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (DC+/DC-) - PE | ≤ 1.1 kV |
| TOV behavior at UT | 174 V DC (5 s / withstand mode) |
| 25 ns | |
| 100 ns | |
| Max. backup fuse with V-type through wiring | 20 A (gG / B at ISCCR> 200 A) |
| Max. backup fuse with branch wiring | 20 A (gG / B at ISCCR> 200 A) |
Additional technical data
| Maximum continuous voltage UC | 135 V AC (for operation in safety lighting systems) |
|---|---|
| Maximum continuous operating voltage UCPV | 150 V DC |
| Short-circuit current rating ISCPV | 1000 A |
| Continuous operating current ICPV | 10 µA |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl) |
| 5 V AC ... 150 V AC (Altitude > 2000 m amsl) | |
| 125 V DC (200 mA DC) | |
| Operating current | 5 mA AC ... 1 A AC |
| 1 A DC (30 V DC) | |
| Connection method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section solid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 6 mm² |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |