View larger
VAL-SEC-T2-2+0-48DC-FM 2907865 PHOENIX CONTACT Type 2 surge arrester
VAL-SEC-T2-2+0-48DC-FM
2907865
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact VAL-SEC-T2-2+0-48DC-FM Type 2 surge arrester is designed to protect sensitive electrical infrastructure from transient voltage spikes and switching surges. Units of this type are commonly installed in distribution boards and control panels to safeguard downstream automation hardware from electrical disturbances. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): Yes
- System configuration IT (EF009927): No
- System configuration TN (EF009928): No
- System configuration TN-C (EF009929): No
- System configuration TN-C-S (EF009933): No
- System configuration TN-S (EF009930): No
- System configuration TT (EF009931): No
- System configuration other (EF009932): No
- Max. continuous voltage AC (EF004198): 75 V
- Max. continuous voltage DC (EF004777): 75 V
- With remote signalling contact (EF000422): Yes
- Signalling at the device (EF004241): Optic
- Category type 2 (EF004230): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2907865 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 50 (C-4-2017) |
| GTIN | 4055626244587 |
| Weight per Piece (excluding packing) | 206.600 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 6000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE | |
| Mounting type | DIN rail mounting |
| Color | light grey RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 48 V DC ... 60 V DC |
|---|---|
| Maximum continuous voltage UC | 75 V DC |
| Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
| 63 A (TWIN ferrule 2 x 10 mm²) | |
| Residual current IPE | ≤ 50 µA DC |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Impulse discharge current (10/350) µs, charge | 2 As |
| Impulse discharge current (10/350) µs, specific energy | 4 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 4 kA |
| Total discharge current Itotal(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 0.2 kA (without backup fuse) |
| 6 kA (for 20 A gG/B backup fuse) | |
| Voltage protection level Up(DC+) - (DC-) | ≤ 0.9 kV |
| Voltage protection level Up(DC+/DC-) - PE | ≤ 0.5 kV |
| TOV behavior at UT | 87 V DC (5 s / withstand mode) |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 20 A (gG / B at ISCCR> 200 A) |
| Max. backup fuse with branch wiring | 20 A (gG / B at ISCCR> 200 A) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl) |
| 5 V AC ... 150 V AC (Altitude > 2000 m amsl) | |
| 125 V DC (200 mA DC) | |
| Operating current | 5 mA AC ... 1 A AC |
| 1 A DC (30 V DC) | |
| Connection method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section solid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 6 mm² |
UL specifications
| SPD Type | 1 |
|---|---|
| Nominal voltage | 60 V DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+) - G | |
| (DC-) - G | |
| Power distribution system | DC |
| Voltage protection rating VPR (DC+) - (DC-) | 800 V |
| Voltage protection rating VPR (DC+) - G | 400 V |
| Voltage protection rating VPR (DC-) - G | 400 V |
| Nominal discharge current In | 20 kA |
| Short-circuit current rating (SCCR) | 50 kA |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Tightening torque | 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |