View larger
VAL-SEC-T2-2+0-220DC-FM 2907875 PHOENIX CONTACT Type 2 surge arrester
VAL-SEC-T2-2+0-220DC-FM
2907875
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
VAL-SEC-T2-2+0-220DC-FM 2907875 Phoenix Contact type 2 surge arrester serves as a protective barrier in industrial control panels, safeguarding sensitive electronics from indirect lightning strikes and switching overvoltages. These components are typically mounted on DIN rails within primary distribution enclosures to divert hazardous electrical transients safely away from downstream circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2907875
- Packing unit: 1 pc
- Catalog page: Page 51 (C-4-2017)
- GTIN: 4055626245003
- Weight per Piece (excluding packing): 226.600 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 97.9 mm
- Width: 25.4 mm
- Depth: 74.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 1.4 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 6000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 2907875 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 51 (C-4-2017) |
| GTIN | 4055626245003 |
| Weight per Piece (excluding packing) | 226.600 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 6000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | light grey RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 200 V DC ... 220 V DC |
|---|---|
| Maximum continuous voltage UC | 250 V DC |
| Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
| 63 A (TWIN ferrule 2 x 10 mm²) | |
| Residual current IPE | ≤ 10 µA DC |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Impulse discharge current (10/350) µs, charge | 0.5 As |
| Impulse discharge current (10/350) µs, specific energy | 0.25 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 1 kA |
| Total discharge current Itotal(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 0.2 kA (without backup fuse) |
| 6 kA (for 20 A gG/B backup fuse) | |
| Voltage protection level Up(DC+) - (DC-) | ≤ 3 kV |
| Voltage protection level Up(DC+/DC-) - PE | ≤ 1.5 kV |
| TOV behavior at UT | 320 V DC (5 s / withstand mode) |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 20 A (gG / B at ISCCR> 200 A) |
| Max. backup fuse with branch wiring | 20 A (gG / B at ISCCR> 200 A) |
Additional technical data
| Maximum continuous voltage UC | 264 V AC (for operation in safety lighting systems) |
|---|
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl) |
| 5 V AC ... 150 V AC (Altitude > 2000 m amsl) | |
| 125 V DC (200 mA DC) | |
| Operating current | 5 mA AC ... 1 A AC |
| 1 A DC (30 V DC) | |
| Connection method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section solid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 6 mm² |
UL specifications
| SPD Type | 4CA |
|---|---|
| Nominal voltage | 220 V DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+) - G | |
| (DC-) - G | |
| Power distribution system | DC |
| Nominal discharge current In | 20 kA |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Tightening torque | 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |