View larger
VAL-MS-CN 1000DC-PV-ST 2801309 PHOENIX CONTACT Replacement plug-in protection for PV arrester combinations f..
VAL-MS-CN 1000DC-PV-ST
2801309
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact replacement plug-in protection for PV arrester combinations provides modular surge suppression within photovoltaic energy networks, safeguarding sensitive DC circuitry from transient overvoltages. Surge protective devices in solar installations limit voltage spikes induced by lightning or switching operations, maintaining continuous operational reliability and protecting downstream electrical infrastructure.
Exact pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- IEC test classification: PV T2
- EN type: T2
- IEC power supply system: DC
- Type: Male
- Product type: Replacement plug
- Product family: VALVETRAB MS
- Installation location: Interior
- Installation location of the disconnect device: Internal
- Accessibility: Accessible
- SPD failure behavior: OCFM (Open-Circuit Failure Mode)
- Surge protection fault message: optical
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Connection method: pluggable
- Width: 17.5 mm
- Height: 52.4 mm
More info
▲| IEC test classification | PV T2 |
| PV T2 | |
| EN type | T2 |
| IEC power supply system | DC |
| Type | Male |
| Product type | Replacement plug |
| Product family | VALVETRAB MS |
| Installation location | Interior |
| Installation location of the disconnect device | Internal |
| Accessibility | Accessible |
| SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
| Surge protection fault message | optical |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Connection method | pluggable |
| Dimensional drawing | |
| Width | 17.5 mm |
| Height | 52.4 mm |
| Depth | 55.3 mm |
| Horizontal pitch | 1 Div. |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PA 6.6-FR |
| Material group | I |
| Housing material | PA 6.6-FR |
| Standby power consumption PC | ≤ 25 mVA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Voltage protection level Up | ≤ 1.9 kV |
| Residual voltage Ures | ≤ 1.9 kV (at In) |
| ≤ 1.4 kV (at 2 kA) | |
| ≤ 1.5 kV (at 5 kA) | |
| ≤ 1.7 kV (at 10 kA) | |
| ≤ 1.8 kV (at 15 kA) | |
| ≤ 2.2 kV (at 30 kA) | |
| ≤ 2.4 kV (at 40 kA) | |
| Response time tA | ≤ 25 ns |
| Protective circuit DC voltage side (DC) | |
| Open circuit voltage UOCSTC | ≤ 487.5 V DC |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Response time tA | ≤ 25 ns |
| Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
| Nominal discharge current In(8/20) µs | 20 kA |
| Continuous operating current ICPV | < 20 µA |
| Maximum continuous operating voltage UCPV | 585 V DC |
| Short-circuit current rating ISCPV | 2000 A |
| Residual voltage Ures | ≤ 1.9 kV (at In) |
| ≤ 1.4 kV (at 2 kA) | |
| ≤ 1.5 kV (at 5 kA) | |
| ≤ 1.7 kV (at 10 kA) | |
| ≤ 1.8 kV (at 15 kA) | |
| ≤ 2.2 kV (at 30 kA) | |
| ≤ 2.4 kV (at 40 kA) | |
| Voltage protection level Up | ≤ 1.9 kV |
| Standby power consumption PC | ≤ 25 mVA |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 7.5g (5-500 Hz/2.5 h/XYZ) |
| Standards/specifications | EN 61643-31 |
| Note | 2019 |
| Standards/specifications | IEC 61643-31 |
| Note | 2018 |
| Mounting type | on base element |