View larger
VAL-MS-CN 1000DC-PV/4+V-FM 2907820 PHOENIX CONTACT Type 2 surge protection device
VAL-MS-CN 1000DC-PV/4+V-FM
2907820
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered to safeguard photovoltaic installations, the Phoenix Contact VAL-MS-CN 1000DC-PV/4+V-FM type 2 surge protection device limits transient overvoltages within direct current circuits. Such devices are installed upstream of sensitive inverters and charge controllers to prevent costly electrical damage caused by atmospheric discharges.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2907820
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 65 (C-4-2017)
- GTIN: 4055626244211
- Weight per Piece (excluding packing): 686.000 g
- Custom tariff number: 85363030
- Country of origin: CN (China)
- Height: 98.57 mm
- Width: 89 mm
- Depth: 64.7 mm
- Degree of protection: IP20 (only when all terminal points are used)
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Altitude: ≤ 4000 mm
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 2907820 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 65 (C-4-2017) |
| GTIN | 4055626244211 |
| Weight per Piece (excluding packing) | 686.000 g |
| Custom tariff number | 85363030 |
| Country of origin | CN (China) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 mm |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 2g (5-500 Hz/2.5 h/XYZ) |
General
| IEC test classification | PV II |
|---|---|
| PV T2 | |
| EN type | T2 |
| SPD failure behavior | OCM |
| Installation location | Inside |
| Accessibility | Accessible |
| Installation location of the disconnect device | Internal |
| Mode of protection | (L+) - (L-) |
| (L+) - PE | |
| (L-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6-FR |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit DC voltage side (DC)
| Maximum continuous operating voltage UCPV | 1170 V DC |
|---|---|
| Short-circuit current rating ISCPV | 2000 A |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 250 µA AC |
| ≤ 20 µA DC | |
| Nominal discharge current (8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Voltage protection level Up | ≤ 3.8 kV |
| Response time tA | ≤ 25 ns |
| Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 125 V AC |
| 30 V DC | |
| Operating current | 3 A AC |
| 3 A DC | |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Screw thread | M5 |
|---|---|
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |