Type 2 surge protection plug Plug-in type 2 surge protection with varistor series connection and gas-filled arc arrester for VAL-MS base element, with thermal control, optical fault indication. Version: 350 V AC with increased lightning current shunt capability.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact model VAL-MS 350 VF-RW ST is a Type 2 surge protection plug designed to safeguard electrical systems and sensitive automation hardware from transient voltage spikes. Devices in this category are commonly deployed in industrial distribution boards to divert high-energy surges safely to earth, preserving downstream equipment integrity. Specific pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 1050280
  • Packing unit: 10 pc
  • Minimum order quantity: 10 pc
  • Note: Made to Order (non-returnable)
  • GTIN: 4055626665177
  • Weight per Piece (excluding packing): 47.430 g
  • Custom tariff number: 85363090
  • Country of origin: DE (Germany)
  • Height: 52.4 mm
  • Width: 17.5 mm
  • Depth: 55.3 mm
  • Horizontal pitch: 1 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Altitude: ≤ 2000 m (amsl (above mean sea level))

More info

▲

Key Commercial Data

Orderkey1050280
Packing unit10 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
GTIN4055626665177
Weight per Piece (excluding packing)47.430 g
Custom tariff number85363090
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
Mode of protectionL-N
L-PE
L-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageoptical

Additional descriptions

NoteUsable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)

Protective circuit

Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 2 mVA
Nominal discharge current In(8/20) µs10 kA
Maximum discharge current Imax(8/20) µs20 kA
Impulse discharge current (10/350) µs, charge1.25 As
Impulse discharge current (10/350) µs, specific energy1.56 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp2.5 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.35 kV (at In)
≤ 1.35 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring125 A (gG)

Connection data

Connection methodpluggable

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.