1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Built for photovoltaic installations, the Phoenix Contact VAL-MS 1500DC-PV/2+V-FM Type 2 surge arrester protects solar power systems from destructive voltage transients caused by atmospheric discharges. These specialty arresters are typically installed in combiner boxes and inverter inputs to secure high-voltage DC configurations. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): Yes
- System configuration IT (EF009927): No
- Category type 2 (EF004230): Yes
More info
▲Key Commercial Data
| Orderkey | 1033725 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626539942 |
| Weight per Piece (excluding packing) | 337.760 g |
| Custom tariff number | 85354000 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 3000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5-500 Hz/2.5 h/XYZ) |
General
| IEC test classification | PV II |
|---|---|
| PV T2 | |
| EN type | T2 |
| IEC power supply system | DC |
| SPD failure behavior | OCM (Open-circuit mode) |
| Connection configuration | Y configuration |
| Installation location | Inside |
| Accessibility | Accessible |
| Installation location of the disconnect device | Internal |
| Mode of protection | (L+) - (L-) |
| (L+) - PE | |
| (L-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6-FR |
| PBT-FR | |
| Degree of pollution | 2 |
| Distance between live and grounded parts | 8 mm |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Additional descriptions
| Note | The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area. |
|---|
Protective circuit DC voltage side (DC)
| Maximum continuous operating voltage UCPV | 1500 V DC |
|---|---|
| Short-circuit current rating ISCPV | 2000 A |
| Continuous operating current ICPV | < 350 µA |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 350 µA DC |
| ≤ 600 µA AC | |
| Standby power consumption PC | ≤ 250 mVA |
| Nominal discharge current (8/20) µs | 15 kA |
| Maximum discharge current Imax(8/20) µs | 30 kA |
| Total discharge current Itotal(8/20) µs | 30 kA |
| Voltage protection level Up | ≤ 5 kV |
| Residual voltage Ures | ≤ 5 kV (at In) |
| ≤ 6 kV (at 30 kA) | |
| Response time tA | ≤ 25 ns |
Additional technical data
| Maximum discharge current Imax(8/20) µs | 40 kA |
|---|---|
| Nominal discharge current In(8/20) µs | 20 kA (4x (5x In| 120 s) | 30 min)) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 30 V AC |
| 30 V DC | |
| Operating current | 1 A AC |
| 1 A DC | |
| Connection method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 16 mm² |
UL specifications
| SPD Type | 1CA |
|---|---|
| Maximum continuous operating voltage MCOV | 1500 V DC |
| Nominal voltage | 1500 V DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+) - G | |
| (DC-) - G | |
| Power distribution system | DC PV |
| Voltage protection rating VPR | 4 kV |
| Nominal discharge current In | 10 kA |
| Short-circuit current rating (SCCR) | 50 kA |
UL indicator/remote signaling
| Operating voltage | 30 V AC |
|---|---|
| 30 V DC | |
| Operating current | 1 A AC |
| 1 A DC | |
| Tightening torque | 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |