PHOENIX CONTACT VAL-MB-T2-750DC-2+V-R VAL-MB-T2-750DC-2+V-R 1376160 PHOENIX CONTACT Type 2/Class II surge protection device for single-pole earthe.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MB-T2-750DC-2+V-R 1376160 PHOENIX CONTACT Type 2/Class II surge protection device for single-pole earthe..

VAL-MB-T2-750DC-2+V-R

1376160

PHOENIX CONTACT

1 Pcs.

Type 2/Class II surge protection device for single-pole earthed DC power systems up to 800 V DC, for rail mounting, with remote indication contact. Model 2 Surge Arrester Surge protective device, acc. to type 2/class II, for grounded, unipolar DC supply systems up to 800 V DC, for DIN rail mounting, with remote indication contact.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Designed for specialized DC networks, the Phoenix Contact VAL-MB-T2-750DC-2+V-R Type 2 surge protection device defends critical direct current infrastructure against damaging transient overvoltages. Equipped with remote signaling capabilities, it alerts control systems when maintenance or module replacement is necessary. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • IEC test classification: T2
  • EN type: T2
  • IEC power supply system: DC
  • Type: DIN rail module, one-piece
  • Product type: Surge arrester
  • Surge protection fault message: Optical, remote indicator contact
  • Insulation characteristics Overvoltage category: III
  • Pollution degree: 2
  • Indicator/remote signaling Connection name: Remote fault indicator contact
  • Switching function: Changeover contact
  • Operating voltage: 5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl)
  • Operating current: 5 mA AC ... 1.5 A AC
  • Cross section AWG: (converted acc. to IEC)
  • Connection method: Screw connection
  • Screw thread: M5
  • Tightening torque: 3 Nm

More info

▲
Technical data

Product properties
IEC test classificationT2
EN typeT2
IEC power supply systemDC
TypeDIN rail module, one-piece
Product typeSurge arrester
Surge protection fault messageOptical, remote indicator contact
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Indicator/remote signaling
Connection nameRemote fault indicator contact
Switching functionChangeover contact
Operating voltage5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl)
5 V DC ... 30 V DC (200 mA DC)
Operating current5 mA AC ... 1.5 A AC
5 mA DC ... 1 A DC

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 35 mm²
Conductor cross section AWG14 ... 2
Remote fault indicator contact
Connection methodScrew connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section rigid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Dimensions
Dimensional drawing
Width71.2 mm
Height120 mm
Depth65.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch4 Div.

Material specifications
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6
PBT
Housing materialPA 6.6

Protective circuit
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Direction of action(L+)-PE & (L-)-PE & (L+)-(L-)
Nominal voltage UN750 V DC
Maximum continuous voltage UC800 V DC
Rated load current IL40 A
Residual current IPE≤ 70 µA DC
≤ 500 µA AC
Standby power consumption PC≤ 70 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Total discharge current Itotal(8/20) µs40 kA
Short-circuit current rating ISCCRmin. 1 kA DC (with maximum backup fuse 40 A gG/1200 V DC)
max. 4 kA DC (with maximum backup fuse 40 A gG/1200 V DC)
Voltage protection level Up≤ 3.3 kV
Residual voltage Ures≤ 3.3 kV (at In)
≤ 2.5 kV (at 3 kA)
≤ 2.7 kV (at 6.25 kA)
≤ 2.9 kV (at 10 kA)
≤ 3.1 kV (at 15 kA)
≤ 4 kV (at 40 kA)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring40 A (gG / 1200 V DC)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 6000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

Standards and regulations
Standards/specificationsIEC 61643-31
Note2018
Standards/specificationsEN 61643-31
Note2019

Mounting
Mounting typeDIN rail: 35 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.