MINI-DC-UPS/12DC/4 2866598 PHOENIX CONTACT Uninterruptible power supply functions as a specialized DC backup unit designed to maintain continuous power for low-voltage control loops and automation components. Such devices ensure that sensitive field instruments and microcontrollers remain active during transient power drops. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 100 V
- Output voltage (EF003933): 10 V
- SNMP (EF005284): No
- Voltage type (EF000187): DC
- Height (EF000040): 99 mm
- Width (EF000008): 67.5 mm
- Depth (EF000049): 107 mm
- Weight (EF000167): 0.491 kg
- Bridging time full load (EF000428): 1200 min
More info
▲Key Commercial Data
| Orderkey | 2866598 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 301 (C-4-2017) |
| GTIN | 4046356418522 |
| Weight per Piece (excluding packing) | 491.200 g |
| Custom tariff number | 85371091 |
| Country of origin | CN (China) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| AC input voltage range | 85 V AC ... 264 V AC |
| Input voltage range DC | 100 V DC ... 350 V DC (UL508: 100...250 V DC) |
| Buffer time | Can be set to: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min; 30 min; permanent |
| Current consumption | 0.65 A (230 V AC) |
| 1.35 A (120 V AC) | |
| Inrush current limiting/I²t | < 1.1 A2s |
| Mains buffering | see diagram |
| Typical response time | 100 ms |
| Power factor (cos phi) | approx. 0.5 |
| Protective circuit | Varistor |
| Input fuse, integrated | 3.15 A (slow-blow, internal) |
Output data
| Nominal output voltage | 12 V DC |
|---|---|
| Setting range of the output voltage (USet) | 10 V DC ... 16 V DC (AC input voltage available, AC input voltage not available: Output voltage depending on the battery voltage: 13.6 V DC ... 9.6 V DC) |
| Nominal output current (IN) | 4 A |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Output current limit | max. 7 A |
| Max. capacitive load | unlimited |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Power loss nominal load max. | 10.5 W |
| Maximum power dissipation in no-load condition | 3.8 W |
| Power dissipation battery operation | 2.9 W |
| Efficiency | > 82 % |
| Residual ripple | < 50 mVPP |
| Peak switching voltages nominal load | < 100 mVPP |
| Connection in parallel | No |
| Surge protection against internal surge voltages | < 35 V DC |
| Feedback resistance | 35 V DC |
General
| IQ technology | no |
|---|---|
| Net weight | 0.45 kg |
| Memory medium | External, rechargeable battery 1.6 Ah / 2.6 Ah |
| Insulation voltage input/output | 4 kV (type test) |
| 2 kV (routine test) | |
| Protection class | II (in closed control cabinet) |
| MTBF (IEC 61709, SN 29500) | |
| > 728000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Connection data, input
| Connection method | Pluggable COMBICON screw connections |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Pluggable COMBICON screw connections |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Connection data for signaling
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 55011 (EN 55022) |
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 6 kV |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 2 GHz |
| Test field strength | 10 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 10 kHz ... 80 MHz |
| Voltage | 10 V |
| Standards/regulations | EN 61000-4-11 |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| EN 61558-2-17 | |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| EN 60204 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Rail applications | EN 50121-4 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |