View larger
QUINT-UPS/ 1AC/ 1AC/500VA 2320270 PHOENIX CONTACT Uninterruptible power supply
QUINT-UPS/ 1AC/ 1AC/500VA
2320270
PHOENIX CONTACT
1 Pcs.
Automation > UPS
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
QUINT-UPS/ 1AC/ 1AC/500VA from Phoenix Contact is an uninterruptible power supply designed to provide robust AC backup power for sensitive industrial control systems and instrumentation. AC UPS units protect vital automation networks from unexpected voltage drops and utility blackouts.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 184 V
- Output voltage (EF003933): 120 V
- Voltage type (EF000187): AC
- Height (EF000040): 130 mm
- Width (EF000008): 125 mm
- Depth (EF000049): 125 mm
- Weight (EF000167): 2.244 kg
- Bridging time full load (EF000428): 3600 min
More info
▲Key Commercial Data
| Orderkey | 2320270 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 280 (C-4-2017) |
| GTIN | 4046356560078 |
| Weight per Piece (excluding packing) | 2,201.000 g |
| Custom tariff number | 85371091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 50 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
Input data
| Nominal input voltage | 240 V AC |
|---|---|
| 100 V AC | |
| 120 V AC -20 % / +15 % | |
| 230 V AC -20 % / +15 % | |
| 100 V AC ... 240 V AC | |
| Input voltage range | 184 V AC ... 264 V AC |
| 96 V AC ... 138 V AC | |
| 96 V AC ... 264 V AC | |
| AC frequency range | 45 Hz ... 65 Hz |
| Buffer period | 1 h (38 AH) |
| Permissible backup fuse | B16 230 V AC |
| Power factor (cos phi) | 0.8 |
Output data
| Nominal output voltage | 120 V AC |
|---|---|
| 230 V AC | |
| Nominal output current (IN) | 4.3 A (120 V AC, -25°C ... 50°C) |
| 2.2 A (230 V AC, -25°C ... 40°C) | |
| POWER BOOST (IBoost) | 5.2 A (120 V AC, -25°C ... 40°C) |
| 2.7 A (230 V AC, -25°C ... 40°C) | |
| Derating | > 50 °C ... 70 °C (2.5%/K) |
| Connection in parallel | no |
| Connection in series | No |
General
| IQ technology | Yes |
|---|---|
| Net weight | 2.2 kg |
| Efficiency | > 98 % (Mains operation) |
| > 98 % | |
| > 86 % | |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| > (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 1.5 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 1.5 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 18 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Screw thread | M4 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 1.5 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 1.5 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 18 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Screw thread | M4 |
Connection data for signaling
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Screw thread | M4 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 62040-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 62040-2 (Class C1) |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 (Class A) |
| UL approvals | UL/C-UL Recognized UL 1778 |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g tv= 90 min. | |
| Rail applications | EN 50121-4 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |