View larger
MCR-SL-CUC-300-I 2308043 PHOENIX CONTACT Universal current transducer
MCR-SL-CUC-300-I
2308043
PHOENIX CONTACT
1 Pcs.
Automation > Current value transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MCR-SL-CUC-300-I is a universal current transducer designed to monitor electrical currents in industrial circuits and convert them into proportional analog signals for control systems. Transducers of this type are widely deployed in electrical distribution panels and machinery to provide safe, isolated feedback for monitoring equipment loads and preventing overcurrent conditions. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Initial value measuring range current (EF008198): 0 A
- End value measuring range current (EF008266): 300 A
- Type of analogy output (EF003958): 4-20 mA
- Integrated configuration function (EF003064): No
- With switching output (EF005225): No
More info
▲Key Commercial Data
| Orderkey | 2308043 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 241 (C-5-2017) |
| GTIN | 4046356434041 |
| Weight per Piece (excluding packing) | 291.000 g |
| Custom tariff number | 90303330 |
| Country of origin | CN (China) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Input data
| Number of inputs | 1 |
|---|---|
| Input current range | 0 A ... 300 A |
| Overload capacity | 3.33 x IIN |
| Frequency measuring range | 20 Hz ... 6000 Hz (0 Hz) |
| Connection method | Cable design: 32 mm diameter |
| Rated frequency: Standard converter | 20 Hz ... 6000 Hz |
| Primary rated current Ipn | 300 A |
Output data
| Output name | Current output |
|---|---|
| Current output signal | 4 mA ... 20 mA |
| Max. output current | < 25 mA |
| Load/output load current output | < 300 Ω |
| Connection method | Screw connection |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 20 V DC ... 30 V DC |
| Max. current consumption | (30 + IOUT) mA |
| Power consumption | 1.65 W |
Connection data
| Conductor cross section solid min. | 0.25 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 10 mm |
General
| Accuracy class | 1 |
|---|---|
| Maximum transmission error | |
| Temperature coefficient, typical | 0.02 %/K (0 ... 60 °C) |
| 0.04 %/K (-40 °C ... 65 °C) | |
| Linearity error | |
| Step response (10-90%) | 150 ms |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V AC |
| Test voltage input/output | 3.5 kV (50 Hz, 1 min.) |
| Test voltage input/power supply | 3.5 kV (50 Hz, 1 min.) |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Color | green |
| Housing material | Frianyl B63 V0 GV30 |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Standards and Regulations
| Noise emission | EN 61000-6-4 |
|---|---|
| Noise immunity | EN 61000-6-2 |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |