OTTA 6-T 0790446 PHOENIX CONTACT Universal terminal block with bolt connection, with disconnect slide, cross..
OTTA 6-T
0790446
PHOENIX CONTACT
1 Pcs.
Automation > Feed-through terminal block
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This Phoenix Contact universal terminal block, identified as OTTA 6-T, features integrated bolt connections and a disconnect slide for flexible circuit configuration. Universal terminal blocks with disconnect functions are widely utilized in measurement and control engineering to isolate specific circuit segments safely during maintenance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of levels: 1
- Number of connections: 2
- Nominal cross section: 6 mm²
- Color: gray
- Insulating material: PA
- Flammability rating according to UL 94: V0
- Rated surge voltage: 8 kV
- Pollution degree: 3
- Overvoltage category: III
- Insulating material group: I
- Connection in acc. with standard: IEC 60947-7-1
- Maximum load current: 36 A (with 6 mm² conductor cross section)
- Nominal current I N: 36 A
- Nominal voltage U N: 800 V (the nominal voltage applies to insulated cable lugs)
- Open side panel: ja
- Width: 11 mm
More info
▲General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Nominal cross section | 6 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
General
| Rated surge voltage | 8 kV |
|---|---|
| Pollution degree | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Connection in acc. with standard | IEC 60947-7-1 |
| Maximum load current | 36 A (with 6 mm² conductor cross section) |
| Nominal current IN | 36 A |
| Nominal voltage UN | 800 V (the nominal voltage applies to insulated cable lugs) |
| Open side panel | ja |
Dimensions
| Width | 11 mm |
|---|---|
| End cover width | 1.5 mm |
| Length | 69 mm |
| Height NS 35/7,5 | 52 mm |
| Height NS 35/15 | 59.5 mm |
| Height NS 32 | 57 mm |
Connection data
| Note | Connection bolts |
|---|---|
| Connection method | Bolt connection |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid min. | 0.1 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 10 |
| Conductor cross section flexible min. | 0.1 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Min. AWG conductor cross section, flexible | 26 |
| Max. AWG conductor cross section, flexible | 10 |
| Cable lug connection according to standard | DIN 46 234 |
| Min. cross section for cable lug connection | 0.1 mm² |
| Max. cross section for cable lug connection | 6 mm² |
| Hole diameter | 4.3 mm |
| Width | 9.6 mm |
| Bolt diameter | 4 mm |
| Cable lug connection according to standard | DIN 46237 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 2.5 mm² |
| Hole diameter | 4.3 mm |
| Width | 9.6 mm |
| Bolt diameter | 4 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |