View larger
PSR-SCF- 24UC/URM/4X1/2X2 2981444 PHOENIX CONTACT Coupling relay
PSR-SCF-24UC/URM/4X1/2X2
2981444
PHOENIX CONTACT
1 Pcs.
Automation > Switching relay
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PSR-SCF-24UC/URM/4X1/2X2 coupling relay operates as a specialized safety interface used to monitor and interrupt critical machine circuits. Safety-rated systems incorporate these devices to ensure dependable signal transmission, prevent hazardous machine restarts, and provide reliable feedback paths in emergency stop architectures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection: Screw connection
- Complete with socket: Yes
- With detachable clamps: No
- With LED indication: Yes
- Voltage type for actuating: AC/DC
- Number of contacts as normally closed contact: 2
- Number of contacts as normally open contact: 4
- Number of contacts as change-over contact: 0
- With forced-guided contacts: No
- Nominal current: 0.052 A
- Degree of protection (IP): IP20
- Width: 40 mm
- Height: 111 mm
- Depth: 55 mm
More info
▲Key Commercial Data
| Orderkey | 2981444 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 279 (C-6-2017) |
| GTIN | 4017918987787 |
| Weight per Piece (excluding packing) | 127.000 g |
| Custom tariff number | 85364900 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
| Rated control circuit supply voltage US | 24 V AC/DC -20 % / +10 % |
|---|---|
| Rated control supply current IS | typ. 52 mA |
| Power consumption at US | typ. 1.25 W |
| Typ. starting time with Us | typ. 10 ms (when controlled via A1) |
| Typical release time | typ. 10 ms (when controlled via A1) |
| Recovery time | < 500 ms |
| Operating voltage display | 1 x green LED |
| Maximum switching frequency | 0.5 Hz |
Output data
| Contact type | 4 enabling current paths |
|---|---|
| 2 confirmation current paths | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2 |
| Interrupting rating (ohmic load) max. | For additional values, see load curve |
| Maximum interrupting rating (inductive load) | 48 W (N/O contact, 24 V DC, τ = 40 ms) |
| 40 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 36 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 35 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 33 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Mechanical service life | 10x 106cycles |
| Switching capacity according to IEC 60947-5-1 | 5 A (24 V (DC13)) |
| 5 A (250 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 127 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | green |
Connection data
| Connection method | Screw connection |
|---|---|
| pluggable | no |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 1 |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 1 |
| Designation | EN ISO 13849 |
| Performance level (PL) | c |
| Category | 1 |
| Safety Integrity Level Claim Limit (SIL CL) | 1 |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 250 V |
| 250 V | |
| Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit (A1/A2) and all output current paths |
| Basic insulation 4 kV between all output current paths | |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 2 ms.) |
| Conformance | CE-compliant |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |