View larger
TC-D37SUB-AIO16-EX-PS-UNI 2902932 PHOENIX CONTACT Module carrier
TC-D37SUB-AIO16-EX-PS-UNI
2902932
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact TC-D37SUB-AIO16-EX-PS-UNI module carrier provides robust mechanical support and structural organization for mounting various electronic submodules in control cabinets. Module carriers streamline rack layouts and maintain orderly arrangement of signal processing units.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2902932
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 165 (C-5-2017)
- GTIN: 4046356697989
- Weight per Piece (excluding packing): 444.440 g
- Custom tariff number: 85366990
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Nominal voltage U N: < 30 V DC (Per signal/channel)
- Max. permissible current: 23 mA (Signal/channel)
- Degree of protection: IP00
- Designation: Power module
- Note: Power supply via 2904673 TC-MACX-MCR-PTB power supply and error signaling module.
- Input voltage: 24 V DC
- Input voltage range: 19.2 V DC ... 30 V DC
More info
▲Key Commercial Data
| Orderkey | 2902932 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 165 (C-5-2017) |
| GTIN | 4046356697989 |
| Weight per Piece (excluding packing) | 444.440 g |
| Custom tariff number | 85366990 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
General
| Nominal voltage UN | < 30 V DC (Per signal/channel) |
|---|---|
| Max. permissible current | 23 mA (Signal/channel) |
| Degree of protection | IP00 |
Supply
| Designation | Power module |
|---|---|
| Note | Power supply via 2904673 TC-MACX-MCR-PTB power supply and error signaling module. |
| Input voltage | 24 V DC |
| Input voltage range | 19.2 V DC ... 30 V DC |
| Input current | ≤ 2 A |
| Redundant supply | yes, decoupled from diodes |
| Polarization and surge protection | Yes |
| Output name | Switching output |
| Contact type | 1 N/C contact (alarm = open) |
| Maximum switching voltage | 50 V DC (0.3 A) |
| Fuse | 2x 2.5 A on PCB, slow-blow (replaceable) |
| Status display | 1 x red LED (error) |
| 2x green LEDs (PWR1 and PWR2) |
Connection 1
| Connection name | Power supply |
|---|---|
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Number of connections | 1 |
| Number of positions | 6 |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection 2
| Connection name | Controller level |
|---|---|
| Connection method | D-SUB pin strip |
| Number of connections | 1 |
| Number of positions | 37 |
Connection 3
| Connection name | X11 |
|---|---|
| Connection method | IDC/FLK pin strip |
| Number of connections | 1 |
| Number of positions | 14 |
| Note | For connecting 16 HART devices to HART multiplexers |
Connection 4
| Connection name | X12 |
|---|---|
| Connection method | IDC/FLK pin strip |
| Number of connections | 1 |
| Number of positions | 14 |
| Note | For connecting a second TC-D37SUB-AIO16-EX-PS-UNI (additional 16 HART channels) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (Please observe module specifications) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 2g, according to IEC 60068-2-6 |
| Maximum altitude | ≤ 2000 m |
Standards and Regulations
| Designation | Air clearances and creepage distances |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 50 V |
| Rated surge voltage | 0.5 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Flammability rating according to UL 94 | V0 |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 2g, according to IEC 60068-2-6 |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 61010 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |