The UM-KS50/32MR/1/ADV551/SC/SO207 2900899 PHOENIX CONTACT Relay Module combines high-density signal switching with interposing relay protection for industrial control panels. Relay modules of this genre are installed to isolate delicate controller circuits from higher-voltage field loads and protect against electrical feedback. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electrical connection, field-sided (EF005525): Screw connection
- Number of poles (EF001391): 50
- Rated voltage (EF000228): 24 V
- Rated current (EF000227): 0.009 A
- Depth (EF000049): 56.5 mm
- Width (EF000008): 267 mm
- Height (EF000040): 127.5 mm
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲Key Commercial Data
| Orderkey | 2900899 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4046356548397 |
| Weight per Piece (excluding packing) | 500.000 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.1 |
| Typical input current at UN | 9 mA (per relay) |
| Protective circuit/component | Damping diode |
| Type of protection | Reverse polarity protection |
| Protective circuit/component | Polarity protection diode |
| Status display/channel | Yellow LED |
Output data
| Contact type | 1 N/O contact |
|---|---|
| Contact material | AgSnO |
| Maximum switching voltage | 230 V AC |
| Limiting continuous current | max. (2x 8 A) |
| Min. switching current | 100 mA |
| Interrupting rating (ohmic load) max. | 48 W (at 24 V DC) |
| 20 W (at 48 V DC) | |
| 18 W (at 60 V DC) | |
| 23 W (at 110 V DC) | |
| 40 W (at 220 V DC) | |
| 500 VA (for 250 V AC) |
Connection data for connection 1
| Connection name | Field level |
|---|---|
| Connection method | Screw connection |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection data for connection 2
| Connection name | Controller level |
|---|---|
| Connection method | Yokogawa KS-compatible |
| Torque | 0.5 Nm |
| Number of connections | 1 |
| Number of positions | 50 |
Connection data for connection 3
| Connection name | Supply |
|---|---|
| Connection method | Screw connection |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Number of positions | 8 |
Supported controller
| Corresponding control | YOKOGAWA CS3000 CentumVP |
|---|---|
| Corresponding I/O card | ADV551 |
| ADV561 | |
| Corresponding control | YOKOGAWA STARDOM |
| Corresponding I/O card | NFDV551 |
| NFDV561 |
Standards and Regulations
| Designation | Air clearances and creepage distances, input/output |
|---|---|
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 6 kV (1.2/50 μs) |
| Insulation | Reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Designation | Air and creepage distances, output/output |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 4 kV (1.2/50 μs) |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |