Functioning as an advanced signal conditioning unit, this UM-KS50/32-MR/21/ADV551/SO207 2311108 PHOENIX CONTACT Active module processes and adapts control signals between field-level sensors/actuators and higher-level control systems. Active interface modules enhance signal fidelity, isolate control loops, and provide necessary power conversion across complex automated production lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2311108
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- GTIN: 4046356145909
- Weight per Piece (excluding packing): 871.000 g
- Custom tariff number: 85364190
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Width: 267.5 mm
- Height: 127.5 mm
- Depth: 44 mm
- Ambient temperature (operation): -20 °C ... 50 °C
- Ambient temperature (storage/transport): -20 °C ... 70 °C
- Nominal input voltage U N: 24 V DC
- Input voltage range in reference to U N: 0.9 ... 1.1
- Typical input current at U N: 7 mA (per channel)
More info
▲Key Commercial Data
| Orderkey | 2311108 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4046356145909 |
| Weight per Piece (excluding packing) | 871.000 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.9 ... 1.1 |
| Typical input current at UN | 7 mA (per channel) |
| Type of protection | Damping diode, polarity protection |
| Protective circuit/component | Damping diode, polarity protection diode |
| Operating voltage display | Green LED |
| Status display/channel | Yellow LED |
Output data
| Contact type | 1 N/O contact |
|---|---|
| Contact material | AgSnO |
| Maximum switching voltage | 230 V AC |
| Limiting continuous current | 2 A (Per channel, pluggable fuse (IEC 6012-3/IV, 2AT)) |
| Maximum inrush current | 8 A (Supply, (V1+, V2+), pluggable fuse (UL 248-14, 250 V, 8AT)) |
| Min. switching current | 100 mA |
| Interrupting rating (ohmic load) max. | 48 W (at 24 V DC) |
| 20 W (at 48 V DC) | |
| 18 W (at 60 V DC) | |
| 23 W (at 110 V DC) | |
| 40 W (at 220 V DC) | |
| 500 VA (for 250 V AC) |
Connection data for connection 1
| Connection name | Field level |
|---|---|
| Connection method | Spring-cage connection |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Connection data for connection 2
| Connection name | Controller level |
|---|---|
| Connection method | Yokogawa KS-compatible |
| Torque | 0.5 Nm |
| Number of connections | 1 |
| Number of positions | 50 |
| Note | Usable system cables: Phoenix Contact YUC50, Yokogawa AKB331 |
Supported controller
| Corresponding control | YOKOGAWA CS3000 CentumVP |
|---|---|
| Corresponding I/O card | ADV551 |
| ADV561 | |
| Corresponding control | YOKOGAWA STARDOM |
| Corresponding I/O card | NFDV551 |
| NFDV561 |
Standards and Regulations
| Designation | Air clearances and creepage distances, input/output |
|---|---|
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 6 kV (1.2/50 μs) |
| Insulation | Reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Designation | Air and creepage distances, output/output |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 4 kV (1.2/50 μs) |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |