Request QuoteProduct Overview
An UM-FLK14/PTS/MSTB/GF-DI interface module from Phoenix Contact creates an efficient physical linkage between process control inputs and field wiring networks. It standardizes connection points to help technicians easily isolate, test, and maintain complex control systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electrical connection, field-sided (EF005525): Screw connection
- Type of electrical connection, control sided (EF008549): Blade terminal
- Number of poles (EF001391): 8
- Rated voltage (EF000228): 30 V
- Rated current (EF000227): 1 A
- Depth (EF000049): 66 mm
- Width (EF000008): 60 mm
- Height (EF000040): 128 mm
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲General
| Max. perm. operating voltage | 50 V DC (25 V AC) |
|---|---|
| Max. perm. current (per branch) | 1 A |
| Max. permissible power (voltage feed) | 3 A |
| Mounting position | any |
| Degree of protection | IP00 |
Connection data for connection 1
| Connection name | Field level |
|---|---|
| Connection method | Screw/plug-in connection |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection data for connection 2
| Connection name | Controller level |
|---|---|
| Connection method | IDC/FLK pin strip |
| Number of connections | 1 |
| Number of positions | 14 |
| Pitch | 2.54 mm |
Standards and Regulations
| Designation | Air clearances and creepage distances |
|---|---|
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 50 V |
| Rated surge voltage | 0.5 kV (1.2/50 μs) |
| Insulation | Functional insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |