View larger
UM-D37SUB/M/HC3/16DO/MR/1/SI 2903733 PHOENIX CONTACT Active module
UM-D37SUB/M/HC3/16DO/MR/1/SI
2903733
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The UM-D37SUB/M/HC3/16DO/MR/1/SI 2903733 PHOENIX CONTACT Active module functions as a specialized electronic signal conditioning and switching unit inside industrial automation networks. Active modules typically incorporate relays, optocouplers, or fuse protection to manage digital outputs, safeguard connected hardware, and isolate control circuits from field power spikes. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electrical connection, field-sided (EF005525): Screw connection
- Type of electrical connection, control sided (EF008549): D-Sub
- Number of poles (EF001391): 50
- Rated voltage (EF000228): 24 V
- Rated current (EF000227): 0.009 A
- Depth (EF000049): 66 mm
- Width (EF000008): 142 mm
- Height (EF000040): 142.5 mm
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲Key Commercial Data
| Orderkey | 2903733 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4046356760775 |
| Weight per Piece (excluding packing) | 628.000 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.9 ... 1.1 |
| Typical input current at UN | 9 mA |
| Typical response time | 5 ms |
| Typical release time | 7 ms |
| Status display/channel | Yellow LED |
Output data
| Contact type | 1 PDT |
|---|---|
| Contact material | AgSnO |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 12 V AC/DC |
| Limiting continuous current | 2 A (Ambient temperature of up to 30°C per path) |
| Min. switching current | 10 mA |
| Interrupting rating (ohmic load) max. | 48 W (24 V DC) |
| 20 W (48 V DC) | |
| 18 W (60 V DC) | |
| 23 W (110 V DC) | |
| 40 W (220 V DC) | |
| 500 VA (250 V AC) |
General
| No. of channels | 16 |
|---|---|
| Mechanical service life | approx. 2x 107cycles |
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
Connection data for connection 1
| Connection name | Controller level |
|---|---|
| Connection method | D-SUB pin strip |
| Number of connections | 1 |
| Number of positions | 37 |
Connection data for connection 2
| Connection name | Field level |
|---|---|
| Connection method | Screw connection |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Number of connections | 1 |
| Number of positions | 50 |
Supported controller
| Corresponding control | HONEYWELL Experion PKS C300/C-Series |
|---|---|
| Corresponding I/O card | TDOB01 (non-redundant) |
| TDOB11 (redundant) |
Standards and Regulations
| Standards/regulations | DIN EN 50178 |
|---|---|
| Rated insulation voltage | 260 V AC |
| Rated surge voltage | 4 kV (basic insulation) |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |