View larger
UM- D37SUB/M/HC3/16DO/MR/1/MT 1083697 PHOENIX CONTACT 16-channel relay module (1 NOC) for Honeywell C300 out..
UM-D37SUB/M/HC3/16DO/MR/1/MT
1083697
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
UM- D37SUB/M/HC3/16DO/MR/1/MT 1083697 PHOENIX CONTACT 16-channel relay module (1 NOC) for Honeywell C300 out. provides galvanic isolation and high-current switching capabilities between delicate controller outputs and demanding plant floor loads. Relay interface blocks protect sensitive automation hardware while managing heavier industrial actuators and solenoids. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electrical connection, field-sided (EF005525): Screw connection
- Type of electrical connection, control sided (EF008549): D-Sub
- Number of poles (EF001391): 37
- Rated voltage (EF000228): 24 V
- Rated current (EF000227): 0.009 A
- Depth (EF000049): 65.5 mm
- Width (EF000008): 175 mm
- Height (EF000040): 128 mm
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|---|
| Note | Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch. |
| The outputs are not suitable for switching different outer conductors. | |
| No additional touch protection is required when using a SELV/PELV voltage (≤ 25 V AC or 60 V DC). | |
| Against adjacent modules in the support rail direction at least one functional insulation on the output-side is complied with. If the application has higher requirements on the insulation (basic insulation or reinforced insulation), then these must be realized through suitable measures (e. g. partition plates). |
Ambient conditions
| Ambient temperature (operation) | -15 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -15 °C ... 50 °C |
| Maximum altitude | ≤ 2000 m |
| Degree of protection | IP00 |
| ≥ IP54 (Installation location) |
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Typical input current at UN | 9 mA |
| Typical response time | 5 ms |
| Typical release time | 7 ms |
| Protective circuit/component | Damping diode |
| Status display/channel | Yellow LED |
Output data
| Contact type | 1 N/O contact |
|---|---|
| Contact material | AgSnO |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 12 V AC/DC |
| Limiting continuous current | 4 A |
| Min. switching current | 10 mA |
| Interrupting rating (ohmic load) max. | 96 W (at 24 V DC) |
| 20 W (at 48 V DC) | |
| 18 W (at 60 V DC) | |
| 23 W (at 110 V DC) | |
| 37 W (at 220 V DC) | |
| 1000 VA (for 250 V AC) |
General
| Mechanical service life | 2x 107cycles |
|---|---|
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
Connection data
| Connection name | Controller level |
|---|---|
| Connection method | D-SUB pin strip |
| Number of connections | 1 |
| Number of positions | 37 |
Connection data 2
| Connection name | Field level |
|---|---|
| Connection method | Screw connection with disconnect knife |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection data 3
| Connection name | Control side |
|---|---|
| Connection method | Flat-ribbon cable connector in acc. with IEC 60603-13 |
| Number of connections | 1 |
| Number of positions | 50 |
Supported controller
| Controller | HONEYWELL Experion PKS C300/C-Series |
|---|---|
| - suitable I/O card | TDOB01 (non-redundant) |
| TDOB11 (redundant) |
Standards and Regulations
| Designation | Air clearances and creepage distances, input/output |
|---|---|
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 6 kV (1.2/50 μs) |
| Insulation | Reinforced insulation |
| Pollution degree | 2 |
| Overvoltage category | III |
| Designation | Air and creepage distances, output/output |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths) |
| Insulation | Basic insulation |
| Pollution degree | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |