View larger
UM- D37SUB/M/HC3/16DI/MR/SI/MT 2900066 PHOENIX CONTACT Active module
UM-D37SUB/M/HC3/16DI/MR/SI/MT
2900066
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Deploying the UM- D37SUB/M/HC3/16DI/MR/SI/MT 2900066 PHOENIX CONTACT active module allows technicians to bridge controller systems and external instrumentation while providing integrated channel-level protection and status indication. Active interface units are commonly installed in manufacturing automation lines to manage input signals safely and reliably. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Interface module
- No. of channels: 16
- Operating mode: 100% operating factor
- Mechanical service life: approx. 2x 10 7 cycles
- Data management status Article revision: 04
- Overvoltage category: II
- Pollution degree: 2
- Rated surge voltage: 0.6 kV (1.2/50 μs)
- Nominal input voltage U N: 48 V DC
- Input voltage range in reference to U N: 0.85 ... 1.1
- Input voltage range: 40.8 V DC ... 52.8 V DC
- Typical input current at U N: 6.5 mA
- Typical response time: 5 ms
- Typical release time: 7 ms
- Protective circuit: Fuse
- Status display/channel: Yellow LED
More info
▲| Product type | Interface module |
| No. of channels | 16 |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Article revision | 04 |
| Insulation characteristics: Air clearances and creepage distances | |
| Insulation | Functional insulation |
| Overvoltage category | II |
| Pollution degree | 2 |
| Air clearances and creepage distances | |
| Rated insulation voltage | 63 V |
| Rated surge voltage | 0.6 kV (1.2/50 μs) |
| Supported controller HONEYWELL Experion PKS C300/C-Series | |
| Suitable I/O card | TDIL01 (non-redundant) |
| TDIL11 (redundant) | |
| TDIL51 (non-redundant) | |
| Nominal input voltage UN | 48 V DC |
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Input voltage range | 40.8 V DC ... 52.8 V DC |
| Typical input current at UN | 6.5 mA |
| Typical response time | 5 ms |
| Typical release time | 7 ms |
| Protective circuit | Fuse |
| Freewheeling diode | |
| Reverse polarity protection | |
| Status display/channel | Yellow LED |
| Switching | |
| Contact switching type | 1 N/O contact |
| Type of switch contact | Single contact |
| Contact material | Ag alloy, hard gold-plated |
| Maximum switching voltage | 36 V DC (60 V DC with damaged gold coating) |
| Minimum switching voltage | 100 mV (12 V DC with damaged gold coating) |
| Limiting continuous current | 50 mA (500 mA with damaged gold coating) |
| Min. switching current | 1 mA (10 mA with damaged gold coating) |
| Interrupting rating (ohmic load) max. | 1.2 W (at 24 V DC) |
| Controller level | |
| Connection method | D-SUB pin strip |
| Number of connections | 1 |
| Number of positions | 37 |
| Field level | |
| Connection method | Screw connection with disconnect knife |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Control side | |
| Connection method | Flat-ribbon cable connector in acc. with IEC 60603-13 |
| Number of connections | 1 |
| Number of positions | 50 |
| Status display present | Yes |
| Width | 344 mm |
| Height | 126 mm |
| Depth | 66 mm |
| Ambient conditions | |
| Degree of protection | IP00 |
| Degree of protection (Installation location) | ≥ IP54 (Installation location) |
| Ambient temperature (operation) | -15 °C ... 50 °C |
| Ambient temperature (storage/transport) | -15 °C ... 50 °C |
| Altitude | ≤ 2000 m |
| Air clearances and creepage distances | |
| Standards/regulations | EN IEC 60664-1 |
| Mounting type | DIN rail mounting |
| Assembly note | in rows with zero spacing |
| Mounting position | any |
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |