View larger
UM- 8 RM-S-G24/21/PLC-MSTB 2311030 PHOENIX CONTACT Active module
UM-8 RM-S-G24/21/PLC-MSTB
2311030
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The UM- 8 RM-S-G24/21/PLC-MSTB 2311030 PHOENIX CONTACT Active module provides electronic switching and signal isolation capabilities within industrial automation architectures. Active modules protect delicate control electronics by buffering inputs and outputs against high-voltage transients and system noise. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Relay Module
- With components: yes
- Overvoltage category: III
- Pollution degree: 2
- Overvoltage category: II
- Pollution degree: 2
- Rated surge voltage: 6 kV (1.2/50 μs)
- Rated surge voltage: 2.3 kV (1.2/50 μs)
- Nominal input voltage U N: 24 V DC (±10 %)
- Typical input current at U N: 200 mA (200 mA supply / ≤ 20 mA input current per signal)
- Switching Contact switching type: Single contact, 1 changeover contact
- Limiting continuous current: 4 A
- Controller level Connection in acc. with standard: IEC 60603-13
- Connection method: IDC/FLK pin strip
- Number of connections: 1
- Number of positions: 14
More info
▲| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
| Product type | Relay Module |
| With components | yes |
| Insulation characteristics: Air clearances and creepage distances, input/output | |
| Insulation | Reinforced insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Insulation characteristics: Air and creepage distances, output/output | |
| Insulation | Functional insulation |
| Overvoltage category | II |
| Pollution degree | 2 |
| Air clearances and creepage distances, input/output | |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 6 kV (1.2/50 μs) |
| Air and creepage distances, output/output | |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 2.3 kV (1.2/50 μs) |
| Nominal input voltage UN | 24 V DC (±10 %) |
| Typical input current at UN | 200 mA (200 mA supply / ≤ 20 mA input current per signal) |
| Switching | |
| Contact switching type | Single contact, 1 changeover contact |
| Maximum switching voltage | 150 V AC/DC (Maximum switching voltage of 230 V AC: the maximum switching voltage of 230 V is only permitted if the same fuse circuit is used. The outputs are not suitable for switching different outer conductors.) |
| Limiting continuous current | 4 A |
| Controller level | |
| Connection in acc. with standard | IEC 60603-13 |
| Connection method | IDC/FLK pin strip |
| Number of connections | 1 |
| Number of positions | 14 |
| Field level | |
| Connection method | Screw connection |
| Number of connections | 1 |
| Number of positions | 12 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Supply | |
| Connection method | Screw connection |
| Number of connections | 1 |
| Number of positions | 2 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| DEROG | |
| Connection method | Screw connection |
| Number of connections | 1 |
| Number of positions | 3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Width | 61 mm |
| Height | 126 mm |
| Depth | 146 mm |
| Ambient conditions | |
| Degree of protection | IP00 |
| Degree of protection (Installation location) | ≥ IP54 (Installation location) |
| Ambient temperature (operation) | -20 °C ... 50 °C |
| Altitude | ≤ 2000 m |
| Air clearances and creepage distances, input/output | |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Air and creepage distances, output/output | |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Mounting type | DIN rail mounting |
| Mounting position | any |