View larger
UM-2KS50-RM/MR/SI/1/SDV541 2319430 PHOENIX CONTACT Relay Module
UM-2KS50-RM/MR/SI/1/SDV541
2319430
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Serving as an electro-mechanical switching interface, this UM-2KS50-RM/MR/SI/1/SDV541 2319430 PHOENIX CONTACT Relay Module safely isolates control circuits from high-power field loads in industrial control systems. These units protect sensitive microprocessors and PLCs from voltage spikes while managing heavy-duty switching duties across various manufacturing machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2319430
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- GTIN: 4046356550031
- Weight per Piece (excluding packing): 1,516.000 g
- Custom tariff number: 85369010
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Width: 425 mm
- Height: 130 mm
- Depth: 95 mm
- Ambient temperature (operation): -20 °C ... 50 °C
- Nominal input voltage U N: 24 V DC
- Input voltage range in reference to U N: 0.9 ... 1.1
- Typical input current at U N: 40 mA
- Protective circuit/component: Damping diode
More info
▲Key Commercial Data
| Orderkey | 2319430 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4046356550031 |
| Weight per Piece (excluding packing) | 1,516.000 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.9 ... 1.1 |
| Typical input current at UN | 40 mA |
| Protective circuit/component | Damping diode |
| Status display/channel | Yellow LED |
Output data
| Contact type | 1 N/O contact per channel |
|---|---|
| Contact material | AgNi (90/10) gold-plated |
| Maximum switching voltage | 230 V AC/DC |
| Limiting continuous current | 4 A (plug-in fuse) |
| Maximum inrush current | Supply 24 V DC/2 A, (P1+, P2+), pluggable fuse (IEC 60127-3/IV, 2AT) |
Connection data for connection 1
| Connection name | Supply |
|---|---|
| Connection method | Screw connection |
| Conductor cross section solid | 0.34 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Number of positions | 6 |
Connection data for connection 2
| Connection name | Field level |
|---|---|
| Connection method | Screw connection with disconnect knife |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Number of connections | 2 |
| Number of positions | 20 |
Connection data for connection 3
| Connection name | Controller level |
|---|---|
| Connection method | Yokogawa KS-compatible |
| Torque | 0.5 Nm |
| Number of connections | 2 |
| Number of positions | 50 |
Standards and Regulations
| Designation | Air and creepage distances, output/output |
|---|---|
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 2.3 kV (1.2/50 μs) |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Designation | Air clearances and creepage distances, input/output |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 6 kV (1.2/50 μs) |
| Insulation | Reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |