Engineered for seamless controller integration, this active module handles signal conditioning and switching tasks within industrial automation loops. Active interface blocks provide dedicated channel management and electrical isolation to protect core control hardware from operational anomalies. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Interface module
- Operating mode: 100% operating factor
- Mechanical service life: 2x 10 7 cycles
- Data management status Article revision: 04
- Pollution degree: 2
- Rated surge voltage: 0.5 kV (Functional insulation)
- Supported controller: YOKOGAWA CENTUM VP Suitable I/O card: ADV551
- Nominal input voltage U N: 24 V DC
- Input voltage range in reference to U N: 0.8 ... 1.2
- Input voltage range: 19.2 V DC ... 28.8 V DC
- Typical input current at U N: 7 mA
- Typical response time: 5 ms
- Typical release time: 6 ms
- Protective circuit: Freewheeling diode; Freewheeling diode
- Status display/channel: green LED
- Switching Contact switching type: 1 N/O contact
More info
▲| Product type | Interface module |
| Operating mode | 100% operating factor |
| Mechanical service life | 2x 107cycles |
| Data management status | |
| Article revision | 04 |
| Insulation characteristics: Air clearances and creepage distances | |
| Overvoltage category | II |
| Pollution degree | 2 |
| Air clearances and creepage distances | |
| Rated insulation voltage | 50 V AC |
| Rated surge voltage | 0.5 kV (Functional insulation) |
| Supported controller YOKOGAWA CENTUM VP | |
| Suitable I/O card | ADV551 |
| ADV561 | |
| NFDV551 | |
| NFDV561 | |
| Nominal input voltage UN | 24 V DC |
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Input voltage range | 19.2 V DC ... 28.8 V DC |
| Typical input current at UN | 7 mA |
| Typical response time | 5 ms |
| Typical release time | 6 ms |
| Protective circuit | Freewheeling diode; Freewheeling diode |
| Status display/channel | green LED |
| Switching | |
| Contact switching type | 1 N/O contact |
| Type of switch contact | Single contact |
| Contact material | AgSnO |
| Maximum switching voltage | 250 V AC |
| 63 V DC | |
| Minimum switching voltage | 5 V (100 mA) |
| Limiting continuous current | 1.5 A (32 °C) |
| 1 A (45 °C) | |
| 0.5 A (50 °C) | |
| Max. total current of voltage supply | 10 A (50 °C) |
| Min. switching current | 1 mA (24 V) |
| Interrupting rating (ohmic load) max. | 48 W (24 V DC) |
| 20 W (48 V DC) | |
| 18 W (60 V DC) | |
| 500 VA (250 V AC) | |
| Controller level | |
| Connection method | Yokogawa KS-compatible |
| Number of connections | 1 |
| Number of positions | 50 |
| Field level | |
| Connection method | Screw connection |
| Number of connections | 32 |
| Number of positions | 2 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Supply | |
| Connection method | Screw connection |
| Number of connections | 4 |
| Number of positions | 2 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Status display present | Yes |
| Dimensional drawing | |
| Width | 271.5 mm |
| Height | 127.5 mm |
| Depth | 60.5 mm |
| Color | green (RAL 6021) |
| Ambient conditions | |
| Degree of protection | IP00 |
| Degree of protection (Installation location) | ≥ IP54 (Installation location) |
| Ambient temperature (operation) | -20 °C ... 50 °C |
| Ambient temperature (storage/transport) | -20 °C ... 80 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Air clearances and creepage distances | |
| Standards/regulations | EN 60664-1 |
| Mounting type | DIN rail mounting |
| Assembly note | in rows with zero spacing |
| Mounting position | any |
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |