PHOENIX CONTACT UK 5-HESILED 60 UK 5-HESILED 60 3004139 PHOENIX CONTACT Fuse modular terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

UK 5-HESILED 60 3004139 PHOENIX CONTACT Fuse modular terminal block

UK 5-HESILED 60

3004139

PHOENIX CONTACT

50 Pcs.

Fuse modular terminal block Fuse terminal block, fuse type: Glass/ceramic/..., fuse type: G/5 x 20, nominal voltage: 60 V, nominal current: 6.3 A, connection type: Screw connection, Sizing cross-section: 1 mm², cross-section: 0.2 mm²- 4 mm², mounting class: NS 35/7.5, NS 35/15, NS 32, colour: black Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 60 V, nominal current: 6.3 A, connection method: Screw connection, Rated cross section: 1 mm2, cross section:  0.2 mm2- 4 mm2, mounting type: NS 35/7,5, NS 35/15, NS 32, color: black

Automation > Fuse terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A fuse modular terminal block, including the Phoenix Contact UK 5-HESILED 60 3004139 PHOENIX CONTACT Fuse modular terminal block, offers streamlined circuit protection and active voltage monitoring within standard industrial distribution boards. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Note regarding marking: For terminal marking, please use marking material with 8.2 mm pitch.
  • Note regarding marking: For lever marking, please use marking material with 6.2 mm pitch.
  • Product type: Fuse terminal block
  • Number of connections: 2
  • Number of rows: 1
  • Potentials: 1
  • Data management status Article revision: 09
  • Insulation characteristics Overvoltage category: III
  • Degree of pollution: 3
  • Fuse type: Glass / ceramics / ...
  • Rated surge voltage: 8 kV
  • Maximum power dissipation for nominal condition: 1.02 W
  • Fuse: G / 5 x 20
  • LED voltage range: 60 V AC/DC
  • LED voltage range: 60 V AC/DC
  • Number of connections per level: 2

More info

Technical data

Notes
Note regarding markingFor terminal marking, please use marking material with 8.2 mm pitch.
Note regarding markingFor lever marking, please use marking material with 6.2 mm pitch.

Product properties
Product typeFuse terminal block
Number of connections2
Number of rows1
Potentials1
Data management status
Article revision09
Insulation characteristics
Overvoltage categoryIII
Degree of pollution3

Electrical properties
Fuse typeGlass / ceramics / ...
Rated surge voltage8 kV
Maximum power dissipation for nominal condition1.02 W
FuseG / 5 x 20
LED voltage range60 V AC/DC

Input data
LED voltage range60 V AC/DC

Connection data
Number of connections per level2
Nominal cross section4 mm²
Level 1 above 1 below 1
Screw threadM3
Tightening torque0.6 ... 0.8 Nm
Stripping length8 mm
Internal cylindrical gageA4
Connection in acc. with standardIEC 60947-7-3
Conductor cross section rigid0.2 mm² ... 4 mm²
Cross section AWG24 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section, flexible [AWG]24 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.25 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.25 mm² ... 4 mm²
Cross-section with insertion bridge, rigid4 mm²
Cross-section with insertion bridge, flexible4 mm²
2 conductors with same cross section, solid0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1.5 mm²
Nominal current6.3 A
Maximum load current6.3 A
Nominal voltage60 V
Nominal cross section1 mm²
Connection in acc. with standardIEC 60947-7-3
Conductor cross section rigid0.2 mm² ... 4 mm²
Cross section AWG24 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross-section flexible (ferrule without plastic sleeve)0.25 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.25 mm² ... 4 mm²
Cross-section with insertion bridge, rigid4 mm²
Cross-section with insertion bridge, flexible4 mm²
2 conductors with same cross section, solid0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible0.2 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1.5 mm²
Nominal current6.3 A
Maximum load current6.3 A
Nominal voltage800 V (As a disconnect terminal block)

Dimensions
Width8.2 mm
Height72.5 mm
Depth on NS 3261.5 mm
Depth on NS 35/7,556.5 mm
Depth on NS 35/1564 mm

Material specifications
Colorblack (RAL 9005)
Flammability rating according to UL 94V2
Insulating material groupI
Insulating materialPA
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Relative insulation material temperature index (Elec., UL 746 B)125 °C

Mechanical properties
Mechanical data
Open side panelNo

Environmental and real-life conditions
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
SpectrumService life test category 1, class B, body mounted
Frequencyf1= 5 Hz to f2= 150 Hz
ASD level1.857 (m/s²)²/Hz
Acceleration0.8g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
Pulse shapeHalf-sine
Acceleration5g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %

Standards and regulations
Connection in acc. with standardIEC 60947-7-3
IEC 60947-7-3

Mounting
Mounting typeNS 35/7,5
NS 35/15
NS 32

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.